4. GF-eXpress Tool
To configure device parameters from GF-eXpress, the function
must be enabled within the TCP/IP communication tool.
Procedure:
1.
Open the GF_eXpress tool and select DRIVES, then select
INVERTER and choose the ADV200 family of drives from the
drop-down menu:
2.
Click Manual to set manual configuration (automatic mode is
not available);
3.
Select the FW of the connected drive (click Select version)
and then set the communication data and press Select.
GEFRAN DRIVES AND MOTION S.R.L.
Via Carducci, 24 - 21040 Gerenzano [VA] ITALY
Ph. +39 02 967601 - Fax +39 02 9682653 - info.motion@gefran.com - www.gefran.com
Manuale scheda EXP-MBTCP-ADV - Pag. 8 / 8
•
Protocol: Modbus
Port: COM, 1
•
•
Baud: 38400
•
Address: 1
Line conf: N,8,1 (frame settings)
•
4.
To enable communication with TCP / IP, open the Target
/ Communication settings drop-down menu and select
ModbusTCP:
5.
Click Activate and then Properties; this calls up a window
where the IP address and Modbus address can be set for the
connected device.
Press OK