Transfer; Wizard; Support - gefran EXP-MBTCP-ADV Manual

Modbus tcp/ip-rtu converter
Table of Contents

Advertisement

BIT 0:
0: indicates an anomaly,
1: the software is active (general check).
BIT 1, Dip-Switch S1-1 configuration (reset default):
0: normal operation,
1: DIP-SWITCH in reset position
BIT 2, Dip-Switch S1-2 configuration (write protection):
0: function off
1: write-protection active;
BIT 3, address configuration
0: static address,
1: dynamic DHCP address
BIT 4
0: normal operation DHCP or static,
1: DHCP IP search failed and system switched to LOCAL-HOST configu-
ration.
COMMUNICATION
Menu for modbus TCP/IP and RTU configuration.
COMMUNICATION/MODBUS CONFIG
IPA
Parameter name
3800
TCP port
TCP port address.
3802
RTU baudrate
Setting the RTU serial communication speed.
3804
RTU parameter
Setting the RTU serial line format.
3806
RTU timeout
Setting the response reception Timeout.
3808
RTU Turnaround
Indicates the permissible slave response delay. If left at 0ms, it is handled
automatically.
3810
RTU Write Protect
Enables the write protection parameters 0 = not protected, 1 = protection
active
3812
RTU Device Address
Setting the device address.
COMMUNICATION/NETWORK CONFIG
IPA
Parameter name
9556
IP Address set
Displays the IP address in use.
9558
IP Netmask set
Enters the subnet IP address entry.
9560
IP Gateway set
Enters the gateway IP address.
9604
Ip Assignment
IP address assignment (DHCO or Static).
9562
IP Address
Enters the network IP address.
9564
IP Netmask
Subnet IP address in use.
9566
IP Gateway
Gateway IP address in use.
Default
502
38400
None,8,1
1500 ms
0 ms
0
1
Default
169.254.10.10
255.255.0.0
0.0.0.0
DHCP
172.16.1.53
255.255.0.0
0.0.0.0
Manuale scheda EXP-MBTCP-ADV - Pag. 6 / 8
9570
Mac address
Displays the drive's MAC address.
9528
WiFi Network Name
Reserved for future use.
9536
WiFi Network Pass
Reserved for future use.
9554
WiFi Network Channel
Reserved for future use.

3.4. Transfer

3.5. Wizard

3.6. Support

88c9b3a00103
0
Import bridge configura-
tion (*): to import a pre-
viously saved configuration.
Export bridge configura-
tion: to export the current
configuration.
Select firmware image file
(*): to update the device FW.
(*) not available in Easy
Wizard to configure the main
Modbus TCP and Modbus RTU
parameters.
Not available in Easy
This section lists all contacts
for support, customer service
and direct links to pages on
the Gefran website.

Advertisement

Table of Contents
loading

Table of Contents