NOTICE!
No mixing valve will work satisfactorily if improperly installed. We suggest, therefore, that you read
these instructions carefully before installing and follow directions as outlined. Handle the mixing valve with care.
The Lawler Series 67 Water Temperature Controller has been carefully assembled and tested at the factory and
set to deliver water at any temperature within the control range stamped on the label. At each inlet of the controller
is a union angle combination stop and check valve with strainer which should be turned open in operation.
CAUTION: When maintaining and adjusting the
mixing valve, all fixtures should be isolated from
use. Lawler Manufacturing Co., Inc. recommends
that you work safely at all times and in a manner
consistent with the OSHA Lock/Tagout standard,
29 CFR 1910.147 and other applicable standards.
This installation & maintenance manual covers all
configurations of the Series 67.
ASSE 1017 Approved
ASSE Lead Free Certified
Certified to CSA B125.3
INSTALLATION &
MAINTENANCE MANUAL
Design and specifications subject to change without notice.
Please refer to temperedwater.com to ensure most
current data sheet and other design solutions.
Series 67
Combination Thermostatic
and Pressure Balanced
Water Controller
CAPACITIES – GPM SERIES 67
Pressure Drop PSI
5
Valve Number
67-10
2.5
67-25
6
1/4 gpm when properly installed in recirculated system.
CAPACITIES – LPM SERIES 67
Pressure Drop PSI
5
Valve Number
67-10
9.4
67-25
22.7
Minimum flow for 67-10 is 1/2 Gallon Per Minute
Minimum flow for 67-25 is 1 Gallon Per Minute
B
72956_6710_STD_DRW_NODIMS.pdf
A
C
DIMENSIONS
Valve Number
A N.P.T.
67-10
1/2"
67-25
3/4"
Dimensions are for reference purposes only. For rough-in dimensions
please refer to Lawler's Revit/BIM models found at temperedwater.com.
temperedwater.com
5330 East 25 th St.
Indianapolis, IN 46218
Phone (317) 261-1212
Fax (317) 261-1208
10
20
30
45
60
Capacity – GPM
3.5
5.5
8
10
12
10
14
18
25
30
10
20
30
45
60
Capacity – LPM
13.2
22.8
30.3
37.8
45.4
37.8
53
68
94.6
113
A
B N.P.T.
C
1/2"
8"
3/4"
8-3/8"
temperedwater.com/patents
80
14
34
80
53
128
M 67 B

Advertisement

loading

Summary of Contents for Lawler 67 Series

  • Page 1 Handle the mixing valve with care. The Lawler Series 67 Water Temperature Controller has been carefully assembled and tested at the factory and set to deliver water at any temperature within the control range stamped on the label. At each inlet of the controller is a union angle combination stop and check valve with strainer which should be turned open in operation.
  • Page 2: Operating Principle

    75°F. A quick test is to momentarily turn on hot water so Lawler Thermostatic Valves adjust for changes in both input the thermostat warms up. If flow then starts, the temperature and pressure, maintaining constant output.
  • Page 3: Checking The Thermostat

    5. When temperature is correct, replace handle screw. If outlet temperature is to be 15°F or more higher than that on the label, contact factory or Lawler representative for a Complete Repair Kits special thermostat.
  • Page 4 Item Description 1/2” Part No. 3/4” Part No. Handle Screw 7628-00 7628-00 Handle 8062-00 8062-00 Cover O-Ring — — Cover Screw 1684-00 1684-00 Cover — — Body Gasket — — Adjusting Screw 8262-00 8262-00 Spindle — — Thermostat — — Thermostat Assembly See Below See Below...
  • Page 5: Typical Installation

    GUARANTEE We guarantee the Lawler Mixing Valve to be free from def ects in workmanship and material, and for a period of one year from date of purchase, will replace any parts found by us to be defective. We will not be held responsible, however, for any labor incidental to, or for any damages caused by defective material.

This manual is also suitable for:

67-1067-25