Emergency Eye Wash Valve
50
40
Operating Principle
This Series 911 Emergency Eye Wash/Face Wash
mixing valve is made of a thermostat element with
a stainless steel sliding piston and liner housed in a
bronze casting. The thermostatic cartridge responds
to temperature changes in the hot and cold water
supplies. In the event the thermostatic element fails
or the hot water supply fails, the valve will provide
full cold water bypass flow.
Note: Valve must be installed with check valves.
If shut off valves are installed in the shower line
for maintenance purposes, provisions shall be
made to prevent unauthorized shut off.
Caution: When maintaining and adjusting the mix-
ing valve, the delivered flushing fluid temperature
shall be 60°F (15°C) to 95°F (35°C). In circum-
stances where chemical reaction is accelerated
by flushing fluid temperature, a medical advisor
should be consulted for the optimum temperature
for each application.
www.lawlervalve.com
Series 911
70
80
60
90
110
120
30
130
E/F
®
CAPACITIES – MODEL 911E/F
Pressure Drop PSI
Tempered Flow
Cold Water Bypass
Setting the Mixing Valve
Caution: When maintaining and adjusting the mix-
ing valve, all fixtures should be isolated from use.
Lawler Manufacturing Co., Inc. recommends that
you work safely at all times and in a manner con-
sistent with the OSHA Lock/Tagout standard, 29
CFR 1910.147 and other applicable standards.
This mixing valve has been set at the factory
to deliver 85°F outlet flow. Should the valve require
adjustment, or an application require a different set
temperature, proceed as follows:
1. Contact the proper medical and safety authorities
to determine the correct water temperature for
the specific application (ie. chemicals).
2. Remove the rounded cover nut on front of the
valve body.
3. Create a draw on the mixing valve by opening a
downstream eye wash fixture.
4. Insert a
/
" allen key into the stem opening of
5
32
the valve and seat in the adjustment screw (not
shown). Set the outlet temperature by turning the
adjustment screw clockwise to reduce tempera-
ture, counterclockwise to increase temperature.
Use the dial thermometer to measure the outlet
temperature.
5. Replace rounded cover nut.
(1)
Installation &
Maintenance Manual
M EFV D
PAT. NO. 5,011,074.
PAT. NO. 5,379,936.
5
10
20
30
45
2
3
5
7
10
1
2
4
5
7

Advertisement

loading

Summary of Contents for Lawler 911 E/F Series

  • Page 1 Setting the Mixing Valve Caution: When maintaining and adjusting the mix- ing valve, all fixtures should be isolated from use. Lawler Manufacturing Co., Inc. recommends that Operating Principle you work safely at all times and in a manner con- sistent with the OSHA Lock/Tagout standard, 29 This Series 911 Emergency Eye Wash/Face Wash CFR 1910.147 and other applicable standards.
  • Page 2 DIMENSIONS: 5. Open the cold water supply. The thermometer 1/2″ inlets & outlets should return to the set temperature. Valve Number Note: The thermometer should be checked at least 911E/F 9″ 4″ 8″ every six months. Replacing the Thermostat Element The thermostat replacement procedure is as follows: 1.
  • Page 3 When supplying 140°F or greater, additional outlet controls should be used. GuARANTEE We guarantee the Lawler Mixing Valve to be free responsible, however, for any labor incidental to, from defects in workmanship and material, and, or for any damages caused by, defective material.
  • Page 4 Series 911E/F Test Record Location _______________________ Parts Break Down Date March April June July Sept March April June July Sept March April June Repair Kits and Assemblies July Item Description Contains Part No. Repair Kit 11-12-15-18-21+B 79854-00 O-Ring & Gasket Kit 10-14-17-22-27 79961-00 Sept...