Single Source Powering - ADC PG-PLUS PCS-718 Technical Practice

19" central office terminal shelf
Hide thumbs Also See for PG-PLUS PCS-718:
Table of Contents

Advertisement

Connections

Single Source Powering

In this configuration, the entire shelf is powered from a single source of –48 Vdc power fused according to
18 on page 24
and
Table 19 on page
A four-position jumper is in place on the TB1 block. This jumper shorts all of the 48 VDC inputs together to
prevent an alarm condition when only one input feed wire is connected. To provide single source powering:
1
Ensure that the ground connection is in place.
2
Connect a wire from the –48A-LOW terminal at TB1
3
Connect a wire from the Battery Return terminal in position 6 of TB1 to the battery return of the CO battery
supply at the fuse panel.
4
The four-position jumper from the –48A-LOW terminal of TB1 to the –48B-HIGH terminal of TB1 should
be installed as shown in
If the –48HIGH and the –48LOW terminals are not jumpered, the COLU power LED blinks because one
of the power rails is missing.
30
25.
Figure
9.
Figure 9. Single Source Power Wiring
January 6, 2003
(Figure
9) to the CO battery supply at the fuse panel.
SCP-PCS718-010-06H