PG-P ECHNICAL RACTICE 19" C ENTRAL FFICE ERMINAL HELF Model List CLEI Code PCS-718 VAMCBC0A~~ Section SCP-PCS718-010-06H...
Page 2
Information furnished by ADC is believed to be accurate and reliable. In no event shall ADC be liable for any damages resulting from the loss of data, loss of use, or loss of profits and ADC further disclaims any and all liability for indirect, incidental, special, consequential or other similar damages.
Page 3
SCP-PCS718-010-06H Using This Technical Practice SING ECHNICAL RACTICE Two types of messages, identified by icons, appear in the text: Notes contain information about special circumstances. Cautions indicate the possibility of equipment damage or the possibility of personal injury. PCS-718 List 1 January 6, 2003...
Page 4
Using This Technical Practice SCP-PCS718-010-06H January 6, 2003 PCS-718 List 1...
SCP-PCS718-010-06H ABLE OF ONTENTS Overview ____________________________________________________________________________ 1 Description and Features........................1 Composite Clock Signals ........................2 Backplane Connections........................2 Power ...........................3 HDSL...........................3 Two-Wire Subscriber Circuits.....................3 Four-Wire Subscriber Circuits.....................3 COLU Edge Card Connectors .....................3 Alarm Cutoff........................16 Alarm Contacts ........................16 Network Interface ......................17 LAN Interface........................18 DSX1 Connections ......................18 PAU/PMU Connector......................19 PMX Connectors .......................20...
Page 6
SCP-PCS718-010-06H Subscriber Connections From CO ..................33 Composite Clock Connections..................40 HDSL Wiring ........................42 External ACO Connection ....................44 Turn-Up and Test ..........................44 Product Support _____________________________________________________________________ 45 Technical Support..........................45 Limited Warranty ..........................45 Returns............................. 45 FCC Class A Compliance........................ 47 Modifications...........................
Page 7
SCP-PCS718-010-06H IST OF IGURES 1. Front View of the PCS-718 COT Shelf......................1 2. PCS-718 Shelf Backplane ..........................2 3. Alarm Relay Contacts from PAU/PMU to COT Shelf Backplane Wire-Wrap Field ........16 4. Modem Connection for FCS-717 Backplane ....................17 5. Null Modem Connection for FCS-717 Backplane ..................18 6.
Page 8
SCP-PCS718-010-06H January 6, 2003 FCS-718 List 1...
Description and Features VERVIEW ® ® The ADC PG-Plus 19-inch Central Office Terminal (COT) shelf, PCS-718 List 1, supports a common management or alarm unit, two multiplexer units and up to twelve universal or integrated PG-Plus Central Office Line Units (COLUs) or up to six PG-Plus Integrated Central Office Line Units (FICOLUs).
EXT ACO pins HDSL pins Figure 2. PCS-718 Shelf Backplane Information in Tables 2 through 17 can be used for diagnostic and troubleshooting procedures under the direction of an authorized ADC technical support representative. January 6, 2003 PCS-718 List 1...
SCP-PCS718-010-06H Backplane Connections The following sections identify each connector by type and function. Table 1. PCS-718 Backplane Connectors Connector Description PAU or PMU connector PMX 1 connector PMX 2 connector J4 - J15 COLU HDSL connectors. The wire-wrap posts are for the HDSL. DB-25 (RS-232) connector 10Base2 LAN connector Frame Ground...
Backplane Connections SCP-PCS718-010-06H Alarm Cutoff The shelf backplane provides a wire-wrap pin for connection to an external alarm cutoff circuit. Alarm Contacts The COT shelf provides access to the PAU/PMU alarm relays by way of wire-wrap pins on the COT shelf backplane.
SCP-PCS718-010-06H Backplane Connections Network Interface The COT shelf supports RS-232 X.25 interfaces through a backplane-mounted DB25 connector. The rear backplane DB-25 is a female connector wired as a Data Terminal Equipment (DTE) interface. The signals and pin assignments for this connector are listed in Table 14.
Backplane Connections SCP-PCS718-010-06H Figure 5. Null Modem Connection for FCS-717 Backplane LAN Interface The COT shelf supports communications between multiple shelves by means of a 10Base2 BNC LAN connector. This feature requires a PMU installed in the COT shelf. Refer to the PMU documentation for additional information on this interface.
Backplane Connections SCP-PCS718-010-06H PMX Connectors J2 and J3 on the COT shelf backplane are the 160-pin DIN-type PMX connectors. Table 16 lists the connector pinouts for PMX 1 (J2 on the backplane). Table 17 on page 21 lists the connector pinouts for PMX 2 (J3 on the backplane).
Page 31
SCP-PCS718-010-06H Backplane Connections Table 17. PMX 2 160-Pin DIN-Type Connector Pin # Row A Row B Row C Row D Row E RDATB1 RDATB2 RDATB3 RDATB4 RDATB5 RSIGB1 RSIGB2 RSIGB3 RSIGB4 RSIGB5 TDATB1 TDATB2 TDATB3 TDATB4 TDATB5 TSIGB1 TSIGB2 TSIGB3 TSIGB4 TSIGB5 CLKB1...
Specifications SCP-PCS718-010-06H PECIFICATIONS Environmental Operating Elevation –200 ft to 13,000 ft ( –60 m to 4,000 m) Temperature –40° F to +150° F ( –40° C to +65°C) Operating Humidity 5% to 95% (noncondensing) Compliance NEBS SR-3580 for Level 3* Human Safety UL 1950 for Restricted Access Emissions Radiation and Immunity...
SCP-PCS718-010-06H Required Tools and Test Equipment NSTALLATION AND EQUIRED OOLS AND QUIPMENT The tools and test equipment required for the installation of the COT shelf are: • Wire-wrap tool for .045-inch square pins • No. 2 Phillips screwdriver • Flat-head screwdriver •...
Power SCP-PCS718-010-06H Powering the Integrated Systems Table 18 summarizes the shelf powering requirements and heat dissipation for the PG-Flex<italics 10>PG Plus COT shelf when it is fully populated with services, a battery voltage of –48.0 V, and with all CO to RT distances at their maximum DSL reach.
SCP-PCS718-010-06H Mounting Powering the Universal Systems Table 19 summarizes the shelf powering requirements and heat dissipation for the PG-Flex<italics 10>PG Plus COT shelf when it is fully populated with services, a battery voltage of –48.0 V, and with all CO to RT distances at their maximum DSL reach.
Wiring Access SCP-PCS718-010-06H Installing the PCS-718 into a CO Equipment Frame The Network Equipment Building Standard (NEBS) limits the maximum dissipation in a 12-inch deep individual CO equipment frame, with open-faced mounting and natural convection cooling, to 946 W (Watts). Refer to each individual line unit technical practice to determine the maximum number of units that can occupy any bay with the 946 W limit.
SCP-PCS718-010-06H Connections ONNECTIONS Ground Connections Frame Ground must be connected to provide a discharge path for outside plant protection circuits. Two Frame Ground termination points are provided on the COT shelf. The J22 and TB1 FGND Frame Ground termination points are electrically equivalent. To ground the COT shelf, do one of the following ground connection options: •...
Connections SCP-PCS718-010-06H Redundant Shelf Powering In this configuration, each circuit card in the COT shelf receives power from two –48 Vdc sources. If one –48 Vdc source is lost, the other –48 Vdc source provides power to the shelf circuit cards. Each –48 Vdc source should be fused according to Table 18 on page 24 Table 19 on page...
SCP-PCS718-010-06H Connections Split Shelf Powering In this configuration, one half of the shelf is powered from one –48 Vdc source, the other half is powered from another –48 Vdc source. Common equipment circuit cards are powered from both sources. If one power supply should fail, one-half of the shelf maintains power.
Connections SCP-PCS718-010-06H Single Source Powering In this configuration, the entire shelf is powered from a single source of –48 Vdc power fused according to Table 18 on page 24 Table 19 on page A four-position jumper is in place on the TB1 block. This jumper shorts all of the 48 VDC inputs together to prevent an alarm condition when only one input feed wire is connected.
SCP-PCS718-010-06H Connections Audible and Visual Alarm Connections Use a wire-wrap tool to terminate the alarm leads from the external alarm equipment on the alarm relay wire-wrap field. See Figure 10 for the location of the alarm relay wire-wrap field. Table 20 on page 32 shows the layout of the wire-wrap pins on the shelf backplane.
Page 42
Connections SCP-PCS718-010-06H Table 20. Alarm Terminations Contact Contact Contact Posts Post Post Post FUNCTION † SYSTEM System indicates a critical, major or minor alarm is active on the COT shelf. CRIT VISUAL Indicates a critical alarm. Connect this relay to the critical alarm visual indicator of the CO alarm system.
SCP-PCS718-010-06H Connections Subscriber Connections From CO Tables 21 through 23 show the assignment of subscriber services from each card slot location to the Telco connectors. Subscriber lines from the CO are connected to the COT shelf by way of 50-pin Telco connectors (P1, P2, P3, and P5).
Page 44
Connections SCP-PCS718-010-06H Table 22. P2 Tip and Ring Pin Assignments COT Shelf Connector COLU Type COT Shelf Assignments Cardslot PLL-720 PLL-721 PLL-722 PLL-723 PLL-724 Ring POTS1 POTS1 POTS1 POTS P2-26 P2-1 POTS2 POTS2 POTS2 P2-27 P2-2 POTS3 POTS3 POTS3 P2-28 P2-3 LU 5 POTS4...
Page 45
SCP-PCS718-010-06H Connections Table 23. P3 Tip and Ring Pin Assignments COT Shelf Connector COLU Type COT Shelf Assignments Cardslot PLL-720 PLL-721 PLL-722 PLL-723 PLL-724 Ring POTS1 POTS1 POTS1 POTS P3-26 P3-1 POTS2 POTS2 POTS2 P3-27 P3-2 POTS3 POTS3 POTS3 P3-28 P3-3 LU 9 POTS4...
Connections SCP-PCS718-010-06H Composite Clock Connections This step is required only if provisioning for DDS circuits. Termination resistors (TERM1 and TERM2) are located below the composite clock wire-wrap pins to provide the correct termination on the composite clock. To connect the clock leads from the Central Office Timing Source Generator to the COT shelf backplane: Connect the first clock pair from the timing source generator to the CC1TIP and CC1RING Connect the second clock pair from the timing source generator to the CC2TIP and CC2RING...
Page 51
SCP-PCS718-010-06H Connections Composite Clock Connections CCITIP CCIRING Shelf-backplane CC2TIP CC2RING CCITIP CCIRING CC2TIP CC2RING Figure 11. Connecting the Composite Clock PCS-718 List 1 January 6, 2003...
Connections SCP-PCS718-010-06H HDSL Wiring J4 - J15 on the PCS-718 backplane correspond to COLU slot numbers LU1 to LU12. Figure 12 shows HDSL connections for J4 and J5. The wire-wrap pin labels for J4 - J15 correspond to the COLU slot number (LU1, LU2, etc.).
Page 53
SCP-PCS718-010-06H Connections Table 28 shows the assignment of each card slot location to the HDSL terminations on the COT shelf backplane. Table 28. PCS-718 HDSL Connections COT Shelf Central Office Line Unit Card Slot HDSL Terminations 2 x 2 Ch. ICOLU 4, 6 Ch.
Turn-Up and Test SCP-PCS718-010-06H External ACO Connection The ACO connection is located to the left handed side of the pin labeled EXT ACO as shown in Figure 13. To control the ACO remotely, connect the ACO to GROUND through a Normally Open, momentary contact switch. Figure 13.
ADC’s Return Material Authorization (RMA) Department. Call or write ADC’s RMA Department to ask for an RMA number and any additional instructions. Use the telephone number, fax number or email address listed below: •...
Page 56
If there is another reason for returning the equipment, please let us know so we can determine how best to help you. Pack the equipment in a shipping carton. Write ADC’s address and the RMA Number you received from the RMA Department clearly on the outside of the carton and return to: ADC DSL Systems, Inc.
The FCC requires the user to be notified that any changes or modifications made to this device that are not expressly approved by ADC Technologies, Inc. voids the user's warranty. All wiring external to the product(s) should follow the provisions of the current edition of the National Electrical Code.
Modifications SCP-PCS718-010-06H CRONYMS Alarm Cut Off American Wire Gauge Central Office COLU Central Office Line Unit Central Office Terminal Digital Data Service Digital Signal One Data Terminal Equipment Electrostatic Discharge FICOLU PG-Flex Integrated Central Office Line Unit HDSL High-bit-rate Digital Subscriber Line Light-Emitting Diode Mechanized Loop Testing NEBS...