Connect the CO Battery

The FCS-717 List 2B COT shelf can be powered from a single battery feed or from a split battery feed.
Use 12 AWG or larger wire (or multiple wires of a smaller gauge) to ensure good power
connections to the PG-Flex system.
Single Battery Feed. For a single battery feed do the following (see
1
Connect the wire from CO battery A to TB1 (-48V_A) termination point.
2
Connect the wire from CO battery return to TB4 (RTN_A) termination point.
3
Connect the CO battery wires from TB1 (-48V_A) on the COT shelf to the equipment bay fuse panel
termination points.
When the FCS-717 List 2B COT shelf is configured for a single battery feed, insert a 10 amp
fuse into the equipment bay fuse panel where the PG-Flex CO battery wire is terminated.
CO Battery A
FCS-717 List 2B
CO Battery Return
10 AMP
Equipment Bay
Fuse Panel
Figure 5. Connecting a Single Battery Feed
January 6, 2003
Figure
5):
Jumper (installed)
TB4
TB3
TB1
RTN_A
RTN_B
-48V_A
Installation and Test
TB2
-48V_B
13