3-6 Transformer

When adjusting the transformer, please note the following points in order to ensure safe use
1) When adjusting the voltage range of the transformer, make sure the voltage range is the same
as the voltage of the Static VAR Generator's main circuit
2) When the transformer is not properly wired, do not start the Static VAR Generator
3) When the main circuit terminal of the Static VAR Generator is powered, please do not directly
adjust the voltage range of the transformer to avoid danger
4) Refer to "Voltage adjustment steps" for instructions on adjusting the transformer
For SVGXXXA43A-XX
Rated primary voltage / frequency: 380/440/480Vac±10% 50Hz/60Hz
Rated secondary voltage / frequency: 230Vac±10% 50Hz/60Hz
Winding
PRI.
SEC.
Meets EN61558; CLASS F (155°C)
Voltage ranges for adapters:
Input voltage
200 ~ 230Vac±10%
380Vac±10%
440 Vac±10%
480 Vac±10%
For SVGXXXA63A-XX
Rated primary voltage / frequency: 525/575/690Vac±10% 50Hz/60Hz
Rated secondary voltage / frequency: 230Vac±10% 50Hz/60Hz
Winding
PRI.
SEC.
Meets EN61558; CLASS F (155°C)
Voltage ranges for adapters:
Input voltage
525Vac±10%
575Vac±10%
690Vac±10%
Circuit Description
0/380/440/480V
0/230V
Circuit Description
0/525/575/690V
0/230V
Table 3-2 Voltage ranges
3-11
Rated Current
3.93A
6.5A
Rated Current
2.16A
6.5A