Lightning Protection Module - Delta SVG300A43A-11 Quick Star

Table of Contents

Advertisement

3-4 Lightning Protection Module

Lightning protection modules used by the full range of Static VAR Generators have the same
specifications, with the following characteristics:
Lightning protection module specifications
FOR SVGXXXA43A-XX
Rated operating voltage Un (V)
Maximum continuous operating voltage Uc (V)
Standard discharge current In (8/20)KA
Maximum discharge current Imax (8/20)KA
Voltage protection level [L-N] Up (KV)
Voltage protection level [N-PE] Up (KV)
Internal overcurrent circuit breaker
Temperature range
Contact performance
FOR SVGXXXA63A-XX
Rated operating voltage Un (V)
Maximum continuous operating voltage Uc (V)
Standard discharge current In (8/20)KA
Maximum discharge current Imax (8/20)KA
Voltage protection level [L-N] Up (KV)
Voltage protection level [N-PE] Up (KV)
Internal overcurrent circuit breaker
Temperature range
Contact performance
Powering system
Circuit breaker
Protection level
Relative humidity
Altitude
Powering system
Circuit breaker
Protection level
Relative humidity
Altitude
TT-TN
380
385
L-N
20
N-PE
20
L-N
40
N-PE
40
1.6
1.2
Internal
Internal
IP20
-40~+85℃
≤95%
150Vdc/2A
3000m
TT-TN
510
690
L-N
20
N-PE
20
L-N
40
N-PE
40
2.5
1.2
Internal
Internal
IP20
-40~+85℃
≤95%
150Vdc/2A
3000m
3-9