A9092T Intelligent Sounder Beacon
Read through these instructions before using this device to ensure correct installation and use!
I. Overview
A9092T Intelligent Sounder Beacon can give audible after being connected to a bus loop. It can be used
with a bus-type fire alarm control panel. After receiving a start command given by the fire alarm control panel
following an accident, the Sounder Beacon will begin to work. At this moment, the Sounder Beacon will give a
harsh audible alarm signal, to remind the persons on the scene of the accident, the fact that a fire has occurred
on the site, quickly and necessity to take related evacuation measures, thus preventing the fire accident from
becoming a major one.
The Sounder Beacon may be used to give audible alarms at the scenes of accidents. It is applicable to
places like high-rise residential buildings, public places, hotels, amusement buildings, factories, shopping
centers, hospitals, schools, office buildings and stock exchanges, and particularly to the places with a low
visibility or the possibility of generation of smoke.
II. Product features
Meet EN54-3.
Designed with an upper cover and a lower cover and installed on an independent base, it can be
installed, debugged and maintained conveniently.
Suitable for wall and ceiling mount application.
Highly efficient LED technology and specially designed lens.
III.
Technical Specification
1. Executive Standard: EN54-3 Type A Sounder
2. Loop input: DC24V(20-28V), ≤2mA(monitoring status), ≤8mA(alarm status)
3. Power consumption: ≤0.2W@DC24V
4. Sound output: ≥73dB(A)@ 1m (667Hz-2000Hz@0.21Hz, Max)
5. Flash rate: 1~2Hz
6. Flash color: RED
7. Protection class: IP21C
Version: 30122800200226
1
8. Operating temperature: -10
℃ ~
+ 55
9. Material Lens/Body: Flame retardant PC/ABS
10. Dimension: φ100mm×100.5mm (with base) , See Fig1.
11. Weight: about 236g
IV.Use and engineering application
1. Wiring:See Fig.2.The sounder beacon is subject to a two-wire non-polarity connection: Terminals 1
and 3 are respectively connected with the terminals L1 and L2 of the loop bus of a compatible fire
alarm control panel.
2. Coding address: The sounder beacon must be encoded address by a special coder(CODER-F900E)
before the installation.Fig.2 shows the wiring diagram of the sounder beacon and coder. After wiring,
press the "#"key to select "324"mode,set the coder with the coding function, then select the correct
address number and press the "RUN/STOP" key to complete the address code setup.(Note: See the
User's Manual of the coder for the detailed operation.)
3. Application: Fig.3 is a schematic diagram of the connection between multiple sounder beacon with a
fire alarm control panel.
Relative Humanity: ≤95% (non-condensing)
Fig.1
Fig.2
2

Advertisement

loading

Summary of Contents for SANJIANG A9092T

  • Page 1 3 are respectively connected with the terminals L1 and L2 of the loop bus of a compatible fire A9092T Intelligent Sounder Beacon can give audible after being connected to a bus loop. It can be used alarm control panel.
  • Page 2 2. If the sounder Beacon is required to be tamper-proof, fix it with ST2.9×5 self-tapping screws thought the tamper-proof hole (see Fig. 5)on the base. Address: 3/F, Guangcai Xintiandi Mansion, Nanshan Road, Nanshan District, Shenzhen, Guangdong, 518054, P.R.China : + 86(755)86226969 : + 86(755)86223939 Http : / /www.sanjiang-security.com Fig. 5...