Cal-Royal 8600 Operation & Installation Manual page 21

Automatic swing door operator
Hide thumbs Also See for 8600:
Table of Contents

Advertisement

8600 Installation Manual
8.19 Special Function Normal
 This setting is used for Access Control options, including Electric Strikes/Locking devices.
 This requires a Wet Input connection to Open. A Wet Input will activate the Strike/Lock and open the door
simultaneously.
 Use the "UP" and "DOWN" buttons to select from Normal, Access or Access→Activate.
Normal = default settings.
Access = only the Strike/Lock will release and the exterior "ACT2" button turns on, so the pedestrian
will need to perform a "Knowing Act" for the door to Open.
Access→Activate = door and Strike/Lock activate simultaneously when a validated credential is
presented.
8.20 In1 Wet Input
 This feature is used with the "Special Function" feature above for external Access Control options that are
either Normally Open or Normally Closed (NO/NC) using the Wet-IN1 input terminal on the board.
 Typical Access Control devices are: Key Pads, Card Readers, Proximity Cards, etc.
 Use the "UP" and "DOWN" buttons to select the NO/NC circuit required by the Access Control device.
 Normally Open = Access Control device will send 12/24vdc power to the control unit.
 Normally Closed = Access Control device takes the 12/24vdc power away from the control unit.
8.21 This Door Overlaps
 This is used for a Double door operator application when there is a door overlap.
 This setting will Enable or Disable the Double swing door Co-ordinate feature.
 Use the "UP" and "DOWN" buttons to Enable or Disable this feature.
8.22 Factory Reset
 This setting will Restore the control unit to its original Factory settings, all current settings will be lost.
 To reset the control to the original settings, push the "UP" button, then push "ENTER" button to confirm.
 You will need to reprogram all features and settings of the control unit.
8.23 Display Light On
 This feature sets the length of time in minutes the LED display will remain on after the last button has been
pushed on the control unit.
8.24 Operator Type
 This setting is used to select which type of Operator functionality you want for this application.
 WARNING: The "Full Automatic" mode can NOT be selected unless all requirements of this installation
complies with the ANSI/BHMA A156.10 Standard for Power Operated Pedestrian Doors including, but not
limited to, Safety Sensors and Guardrails.
 Use the "UP" and "DOWN" buttons to select.
8.25 Safety 2 Inhibit
 Safety 2 will be deactivated at the point where the Safety sensor would pick up a wall or fixed object adjacent
to the door.
 This setting will inhibit the Safety Sensor (back side of the door) in order to allow the door to fully open.
(Access/Access→Activate).
(Normally Opened/Normally Closed)
(Yes/No)
(Yes/No)
Time (01-30 minutes)
(Low Energy/Full Automatic)
at (30%-98%)