continue to run the supply fan until the heat exchanger has cooled sufficiently. This feature will help prolong the life of
the heat exchanger. The temperature controller must be replaced if the fan motor does not shut off after the heat
exchanger has cooled down.
Temperature Controller Protocols
Fan Turns on at 90 °F
Out # 2 is set at 280ºF (This will cycle the burner off 280ºF and back on at 275ºF.) If the burner reset light goes on; you
need to go into the burner compartment. For the Beckett CF800 oil burner the Beckett Genisys controller located on
the control panel must be pressed.
There is a high limit switch set at 295ºF supply temperature (This will cause burner to go out on high temp.)
During cool down the unit cools to 80 °F and then shuts down.
ELECTRICAL
Ensure all conduit (BX) connectors are tight. Open control panel door and burner compartment and check connections
are tight and no frayed wires exposed.
FAN
Check for dust or dirt build up on blades. Run heater to check for fan vibration. Replace fan blade if vibration is
noticeable. The flow of combustion and ventilation air must not be obstructed. Be sure to check the fan assembly and
ensure that the motor and blade are operating properly.
MOTOR
No lubrication is necessary since the bearings are the sealed type. Clean motor of existing dust or dirt.
HEAT EXCHANGER
If a smoky condition continues even after adjusting the air assembly, the heat exchanger should be thoroughly
cleaned.
FUEL FILTER (OIL OPERATION)
Replace cartridge every six months of normal usage.
NOTE: FLOW OF COMBUSTION AND VENTILATION AIR CANNOT BE OBSTRUCTED
FLAME DETECTOR (OIL OPERATION)
When doing maintenance, turn on machine and run. After having machine run for a few minutes, press red button on
primary control. Hold for one second and then release. If light flashes once or twice or three times, cad cell is
functioning properly. If flashes four times, check alignment and proper flame. If correct a cleaning of the face of the
cad cell with a soft non-abrasive cloth is recommended. If light flashes 4 times, follow above steps. If flashing four
times persists, replace cad cell.
Tel: (905) 793-2525 | Fax: (905) 793-8768 |
1-800-486-4328
1-204-633-1999
LED FLASHES
1
2
3
4
CAMPO EQUIPMENT CO. LTD. (ECOBLAZE)
6 Carson Court, Brampton, ON, CANADA, L6T 4P8
100 Eagle Drive
Winnipeg, MB Canada
CAD CELL RESISTANCE
0-400 Ohms
400-800 Ohms
800-1600 Ohms
>=1600 Ohms
www.campoequipment.com