IF HEATER FAILS TO START
1.) PRESS AND HOLD THE RED BUTTON ON THE BECKETT GENISYS CONTROLLER LOCATED ON THE
CONTROL PANEL FOR 3 SECONDS TO RESET.
2.) CHECK FUEL LEVEL, FILTER, NOZZLE AND SUCTION TUBING.
3.) ENSURE PROPER POWER SUPPLY AND WIRE GAUGE IS BEING USED.
4.) IF HEATER FAILS TO IGNITE AFTER 3 ATTEMPTS, CALL YOUR SUPPLIER FOR SERVICE.
NOTE: IF UNIT HAS BEEN RESET A NUMBER OF TIMES WITHOUT IGNITION -- DO NOT ATTEMPT TO START
THE HEATER: CONTACT A QUALIFIED SERVICE TECHNICIAN.
NOTE: IN OIL OPERATION IF UNIT HAS BEEN RESET A NUMBER OF TIMES WITHOUT IGNITION THERE WILL
BE AN ACCUMULATION OF OIL IN THE COMBUSTION CHAMBER! DO NOT ATTEMPT TO START THE
HEATER: CONTACT A QUALIFIED SERVICE TECHNICIAN.
CAUTION
1.) DO NOT SHUT OFF BY DISCONNECTING SUPPLY CORD. THE HEAT EXCHANGER SHOULD BE
PROPERLY COOLED BEFORE POWER SHUTDOWN.
2.) ALWAYS MAINTAIN ADEQUATE FUEL SUPPLY.
3.) DO NOT PLUG ANYTHING OTHER THAN THE THERMOSTAT INTO THE "REMOTE STAT" PLUG.
4.) FOLLOW ELECTRICAL REQUIREMENTS SHOWN ON RATING PLATE AND/OR ELECTRICAL
REQUIREMENTS SECTION OF THIS MANUAL.
5.) DO NOT START THE HEATER WHEN EXCESS OIL HAS ACCUMULATED IN CHAMBER.
6.) DO NOT FILL TANK WHILE UNIT IS OPERATING.
7.) IN NO CASE SHOULD POWER CABLES BE SMALLER THAN WHAT IS STIPULATED ON NAMEPLATE
AND INSTRUCTION MANUAL.
8.) DO NOT USE GASOLINE, CRANKCASE OIL OR HEAVIER THAN NO. 2 FURNACE OIL.
9.)
DO NOT START THE HEATER WHEN THE CHAMBER IS HOT
10.) DO NOT FILL THE TANK WHILE THE UNIT IS OPERATING
11.) DO NOT TAMPER WITH THE UNIT. HAVE A COMPETENT SERVICE-MAN MAKE ANY ADJUSTMENTS
12.) MAX OUTLET TEMPERATURE OF 280F
13.) AT INSTALLATION ELEVATIONS ABOVE 2000 FT (610m), THE APPLIANCE SHALL BE DERATED 4
PERCENT FOR EACH 1000 FT (305m) OF ELEVATION ABOVE SEE LEVEL
14.) DO NOT USE THIS UTILITY HEATER IF ANY PART HAS BEEN UNDER WATER. IMMEDIATELY CALL A
QUALIFIED SERVICE TECHNICIAN TO INSPECT THE HEATER AND REPLACE ANY CONTROL WHICH
HAS BEEN UNDER WATER.
ELECTRICAL REQUIREMENTS: 15 AMPS

INSTALLATION INSTRUCTIONS

1.) The recommendations of local authorities having jurisdiction must be followed. For
recommended installation practices refer to C.S.A. standard B139. (CANADA)
2.) When firing the unit in an enclosed area allow 1 square inch per thousand BTU's (refer to
C.S.A. B139-1962) to allow the free entry of the air required for operation.
3.) For electrical supply:
4.) Do not operate the unit in partly ventilated areas without a flue pipe or in close proximity to
combustible surfaces or materials. Non Combustible floor must extend 6 feet on all sides of
the unit.
Tel: (905) 793-2525 | Fax: (905) 793-8768 |
1-800-486-4328
1-204-633-1999
120 Volts 15 amps
CAMPO EQUIPMENT CO. LTD. (ECOBLAZE)
6 Carson Court, Brampton, ON, CANADA, L6T 4P8
100 Eagle Drive
Winnipeg, MB Canada
www.campoequipment.com
sales@hermannelson.com
www.hermannelson.com
| 10
P a g e

Advertisement

loading