Installation Procedure
Spacing requirements
5.91(150) or more
5.91(150) or more
CAUTION
• The indoor unit must be installed according to the
specified distances in order to permit accessibility
from each side, to guarantee correct operation,
maintenance, and repair of the unit.
The components of the indoor unit must be reachable
and removable under safe conditions for people and
the unit.
• Do not carry the unit by holding the refrigerant or
drain pipes to avoid product damage.
• Carry the unit by holding the hanger plates located on
the corners of the unit.
10
English
Step 3 Optional: Insulating the body of
the indoor unit
Unit: inch(mm)
Cut openings in the insulation for unit refrigerant and
drain pipes.
59.06(1500) or more
Insulate the end of the pipe and some curved area by
using separate insulator.

Step 4 Installing the indoor unit

When deciding on the location of the air conditioner the
following restrictions must be taken into account.
1 Place the pattern sheet on the ceiling at the location
5.91(150) or more
• Since the diagram is made of paper, it may shrink
2 Insert bolt anchors, use existing ceiling supports or
Hole in anchor
Hole in plug
where you want to install the indoor unit.
NOTE
or stretch slightly due to temperature or humidity.
For this reason, before drilling the holes, be sure
to maintain the correct dimensions between the
markings.
construct a suitable support as shown in figure.
Concrete
Suspension bolt (3/8"(9.52mm) or M10)
Insert