DISCRETE OUTPUT FUNCTIONAL BLOCKS (R3Do [0] through [2])
NodeObject FUNCTIONAL BLOCKS
NETWORK
TYPE
VARIABLE
{Range}
{Default}
nviRequest
SNVT_obj_request
{Usable RQ
RQ_NORMAL
RQ_REPORT_MASK
RQ_UPDATE_STATUS}
nvoStatus
nvoFileDirectory
SNVT_address
nvoCommErr
SNVT_count
{0-65535}
{0}
nvoCardStatus
SNVT_state
{0 or 1}
{0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0}
nvoCardErr
SNVT_state
{0 or 1}
{0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0}
CONFIGURATION
TYPE
PROPERTY
{Range}
{Default}
cpMaxSendTime
SCPTmaxSendTime
{0.0-6653.4}
{10.0}
cpMinSendTime
SCPTminSendTime
{0.0-6653.4}
{0.0}
R3Do [X]
nviDoch01
:
nviDoch16
SNVT_switch
nvoDoState
SNVT_state
EXPLANATIONS
Used for integration tools such as LonMaker.
Used for integration tools such as LonMaker.
• nviRequest RQ_NORMAL
0 is set at nvoStatus.
• nviRequest RQ_REPORT_MASK
report_mask bit is set at nvoStatus.
• nviRequest RQ_UPDATE_STATUE
0 is set at nvoStatus.
• 1 is set at invalid_id when any value other than the above
three types is set at nviRequest.
Used for integration tools such as LonMaker.
Counted in internal communication errors.
Reset to 0 after the count has reached 65535.
Indicates that I/O modules are mounted in each slot.
Bit 0 through bit 15 are applied for slot 1 through 16.
0 : Not mounted
1 : Mounted
Indicates error status for each module/slot.
Bit 0 through bit 15 are applied for slot 1 through 16.
0 : Normal
1 : Error
EXPLANATIONS
Sending time intervals of nvoVal [0 – 15]
Network variables are sent out in this time intervals even
when there is no change in input signals.
Minimum sending time intervals of nvoVal [0 – 15]
This minimum time intervals is maintained even when the
input signals changes faster than it.
R3-NL1
P. 6 / 8
EM-8427 Rev.5