Functional Blocks - M-system R3-NL1 Instruction Manual

Lonworks interface module
Hide thumbs Also See for R3-NL1:
Table of Contents

Advertisement

I/O COMBINATIONS
A dedicated Device File for each I/O device depending upon I/O combinations is required to set up the R3-NL1 using an
integration tool such as Lon Maker.
On-line download is available for Device Image files at http://www.m-system.co.jp/.
Functional Blocks usable for respective files are not identical to all. Refer to the table below.
ANALOG INPUT / OUTPUT
NO. of DATA
DEVICE IMAGE
(APB FILE)
INPUT OUTPUT
16
0
R3NL1_1_101.APB
12
4
R3NL1_2_101.APB
8
8
R3NL1_3_101.APB
4
12
R3NL1_4_101.APB
0
16
R3NL1_5_101.APB
DISCRETE INPUT / OUTPUT
NO. of DATA
DEVICE IMAGE
(APB FILE)
INPUT OUTPUT
0
48
R3NL1_6_101.APB
48
0
R3NL1_7_101.APB

FUNCTIONAL BLOCKS

NODE OBJECT
nviRequest
NVI 1
SNVT_obj_request
Configuration Properties
cpMaxSendTime
cpMinSendTime
NodeObjet, GetValue [0 ... 15] (Can be defined from 0 to 15)
NodeObjet, GetValue [0 ... 11], SetValue [0 ... 3]
NodeObjet, GetValue [0 ... 7], SetValue [0 ... 7]
NodeObjet, GetValue [0 ... 3], SetValue [0 ... 11]
NodeObjet, SetValue [0 ... 15]
NodeObjet, R3Do [0 ... 2] (One (1) block can handle 16 contacts.)
NodeObjet, R3Di [0 ... 2]
NodeObject
NVO 1
NVO 2
NVO 3
NVO 4
NVO 5
: SCPTmaxSendTime
Input data sending intervals
: SCPTminSendTime
Input data minimum sending intervals
USABLE FUNCTIONAL BLOCKS
USABLE FUNCTIONAL BLOCKS
nvoStatus
SNVT_obj_status
nvoFileDirectory
SNVT_address
nvoCommErr
Number of internal
SNVT_count
communication errors
nvoCardState
Each module status
SNVT_state
nvoCardErr
Each module's error status
SNVT_state
R3-NL1
P. 4 / 8
EM-8427 Rev.5

Advertisement

Table of Contents
loading

Table of Contents