V2 AYROS-230V Manual page 47

230v electro-mechanical irreversible rack actuator for sliding gates up to 1200 kg
Table of Contents

Advertisement

Available languages

Available languages

PARAMETER
VALUE
FrEn
1 - 1 0
0
rA.AP
0 - 1 00
rA.Ch
0 - 1 00
St .AP
PAUS
ChiU
no
St .Ch
StoP
APEr
St .PA
ChiU
no
PAUS
SP.AP
PAUS
ChiU
no
DESCRIPTION
Brake Function
When a sliding motor is used with a very heavy gate, because of the
inertia, the gate does not block immediately when stopped and its motion
can last for another 10 cm, compromising the working of the safety
devices.
This menu allows enabling the brake function thanks to which it is
possible to block immediately the gate after a control or the intervention
of a safety device.
The brake power is proportional to the set value
WARNING: each braking entails a mechanical stress to the
components of the motor. We suggest to set the minimum value
with which there is a satisfactory stop distance.
Function deactivated
Slow down in opening
This menu allows regulating the percentage of the ride/drive that is carried
out at reduced speed during the last opening stretch
Slow down in closing
This menu allows regulating the percentage of the ride/drive that is carried
out at reduced speed during the last closing stretch
Start command during the opening phase
This menu allows fixing the control unit conduct in case it receives a Start
command during the opening phase
The gate stops and goes to pause
The gate immediately starts closing
The gate go on with the opening phase (command is ignored)
Start command during the closing phase
This menu allows fixing the control unit conduct in case it receives a Start
command during the closing phase
The gate stops and its cycle is considered as finished
The gate opens again
Start command during the pause
This menu allows fixing the control unit conduct in case it receives a Start
command when the gate is open during its pause phase
The gate starts closing
Command is ignored
Ch.AU
The pause time is reset (
Pedestrian Start during the partial opening phase
This menu allows fixing the control unit conduct in case it receives a
Pedestrian Start command during the partial opening phase.
WARNING: a Start command in any phase of partial opening will
cause the total opening; the Start Pedestrian command is always
ignored during a total opening
The gate stops and goes to pause
The gate immediately starts closing
The gate goes on with the opening phase (command is ignored)
)
- 45 -
DEFAULT
MEMO
5
15
15
PAUS
StoP
ChiU
PAUS

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ayros400d-230vAyros800d-230vAyros1200d-230v

Table of Contents