Installation; Installation - Foundation - Trane BAYBARO300 Series Installation Manual

Barometric relief damper
Table of Contents

Advertisement

Installation

WARNING
Hazardous Service Procedures!
Failure to follow all precautions in this manual and on
the tags, stickers, and labels could result in death or
serious injury.
Technicians, in order to protect themselves from
potential electrical, mechanical, and chemical
hazards, MUST follow precautions in this manual and
on the tags, stickers, and labels, as well as the
following instructions: Unless specified otherwise,
disconnect all electrical power including remote
disconnect and discharge all energy storing devices
such as capacitors before servicing. Follow proper
lockout/tagout procedures to ensure the power can
not be inadvertently energized. When necessary to
work with live electrical components, have a qualified
licensed electrician or other individual who has been
trained in handling live electrical components perform
these tasks.
1. Remove horizontal access panel (item 1) from the unit.
Figure 5. Remove horizontal access panel
2. Prepare Barometric Relief Kit: :
a. Field installed kits: Remove packaging material
and all shipping screws from parts. Remove parts
from box.
b. Shipped with unit: Remove shipping screws from
damper assembly and shipping brackets. Discard
shipping brackets. Remove parts from box and
packaging material.
ACC-SVN156E-EN
Installation — Foundation™
1. Assemble block-off panel:
a. When using duct opening furthest from
evaporator coil: Attach 4, 5 and 7 using six
screws.
Figure 6. When using duct opening furthest from
evaporator coil.
b. When using duct opening closest to evaporator
coil: Attach 4 and 5 using three screws to build
right block-off. Attach 3 and 6 using three screws to
build left block-off.
Figure 7. When using duct opening closest to
evaporator coil
2. Cut one piece of gasket (item 9) to a length of
4.3 inches. Attach to the bottom of the side block-off
panel (item 4) leaving a 0.5 inch gap from surface A.
Note: Applicable to both return duct opening
configurations.
7

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fiabarm003 series

Table of Contents