SUPERSEDES: January 14, 2021
Plant ID No. 001-5000
DESCRIPTION:
The 007e-2 is a variable speed, high-efficiency wet rotor circulator with an ECM, permanent mag-
net motor. Its ECM performance is equivalent to the legendary Taco 007 and ideal for hydronic
systems zoned with circulators or zone valves. It reduces power consumption by up to 85% com-
pared to equivalent AC permanent split capacitor circulators.
APPLICATION:
• Maximum operating pressure: 125 psi (8.6 bar)
• Maximum water temperature: 230°F (110ºC)
• Electrical specifications:
Voltage: 110-120V, 50/60 Hz, single phase
Maximum operating power: 44W
Maximum amp rating: 0.54
• Equipped with a cast iron casing and should be used for closed loop systems only
• Not suitable for open loop potable water or chilled water systems
• Taco circulator pumps are for indoor use only – employer uniquement a l'interieur
• Acceptable for use with water or maximum of 50% water/glycol solution
• Not recommended for systems designed for constant circulation
FEATURES:
• ECM performance equivalent to the legendary Taco 007 circulator
• Multi-color LED display showing power on and error code diagnostics
• Use with a Taco Zone Valve Control (ZVC) or Switching Relay (SR) for ON/OFF operation
• Nut capture feature on flanges for easier fit up
• Dual electrical knockouts and 6" stranded wire leads for easy wiring
• Double insulated - no ground-wire required
• Whisper quiet operation
• BIO Barrier
®
protects the pump from system contaminants
• SureStart
- automatic unblocking and air purging mode
®
• Optional 2-way universal flange model for easy fit-up to any flange orientation
• Integral Flow Check (IFC
• Green Mode active system monitoring and power optimization
WARNING: Do not use in swimming pool or spa areas. Pump has not been investigated for these applications.
AVERTISSEMENT: Ne pas utiliser dans une piscine ou un spa. La pompe n'a pas été étudiée pour ces applications.
CAUTION: The addition of petroleum based fluids or certain chemical additives to systems using TACO equipment voids the war-
ranty. Consult factory for fluid compatibility.
ATTENTION: L'ajout de liquides à base de pétrole ou de certains additifs chimiques à des systèmes utilisant un équipement TACO
annule la garantie. Consultez le fabricant pour connaître la compatibilité de liquides.
CAUTION: Installations at elevations over 5000 feet must have higher fill pressure of 20 psi minimum to prevent pump cavitation
and flashing. Premature failure may result. Adjust expansion tank pressure to equal fill pressure. A larger size expansion tank may
be required.
ATTENTION: Des installations à des altitudes de plus de 1600 mètres doivent présenter une pression de remplissage plus élevée
de 20 psi au minimum afin d'éviter toute cavitation ou flashing de la pompe. Une défaillance prématurée peut en résulter. Réglez
la pression du réservoir d'expansion de façon qu'elle soit égale à la pression de remplissage. Un réservoir d'expansion d'une taille
supérieure peut être nécessaire.
Instruction Sheet
ECM High-Efficiency Circulator
007e
-2
®
) included - Field installed
®
®
-1-
102-517A
EFFECTIVE: August 16, 2021
Figure 1:
Standard flange model: 007e-2F2
Optional 2-way flange model: 007e-2F4

Advertisement

Table of Contents
loading

Summary of Contents for Taco Comfort Solutions 007e-2

  • Page 1 DESCRIPTION: Figure 1: The 007e-2 is a variable speed, high-efficiency wet rotor circulator with an ECM, permanent mag- net motor. Its ECM performance is equivalent to the legendary Taco 007 and ideal for hydronic systems zoned with circulators or zone valves. It reduces power consumption by up to 85% com- pared to equivalent AC permanent split capacitor circulators.
  • Page 2 Figure 2:...
  • Page 3 Figure 3: KEY: VI, V2, V3 = SHUT-OFF ISOLATION VALVE P = TACO CIRCULATOR WITHOUT IFC INSTALLED FF = FAST FILL BOILER FEED VALVE PV4 = PURGE VALVE ZV = ZONE VALVE RECOMMENDED PURGING STEPS: 1. CLOSE V1, PV4, V2 2.
  • Page 4 Location: The circulator can be installed on the supply or return side of the boiler but for best system performance, it should always pump away from the expansion tank. See piping diagrams in Figure 2 and Figure 3. CAUTION: Do not use flat rubber gaskets. Only use O-ring gaskets provided or leaks may result. Warranty will be void. Mounting position: Circulator must be mounted with the motor in the horizontal position.
  • Page 5: Normal Mode

    Green Mode: After 7 days of constant circulation, the 007e will self-adjust to Green Mode curve (low proportional pressure) for power optimization. See Green mode curve above. When the 007e-2 cycles OFF, the circulator resets to original Normal Mode curve.
  • Page 6: Control Panel

    7. Troubleshooting the error codes: Listed below are potential diagnostic error codes which will appear on the LED display in case of a malfunction. CONTROL FAULTS CAUSES REMEDIES PANEL Increase the system suction Suction pressure is LED on pressure within the insufficient - cavitation The circulator is permissible range.
  • Page 7 Replacement Parts Replacement Parts 198-213 RP Casing O-ring 198-213 RP Casing O-ring 198-214 RP Wiring plug connector (green) 198-214 RP Wiring plug connector (green) 198-215 RP Terminal box cover (black) 198-215 RP Terminal box cover (black) 198-217 RP 198-217 RP Terminal box cover screws (5 per bag) Terminal box cover screws (5 per bag) 0010-025 RP...
  • Page 8: Instruction Sheet

    102-563 Stainless Steel, Variable Speed ® High-Efficiency ECM Circulator Instruction Sheet SUPERSEDES: February 23, 2021 EFFECTIVE: August 16, 2021 Plant ID No. 001-5023 DESCRIPTION: Figure 1: The 007e® stainless steel is a variable speed, high-efficiency wet rotor circulator with ECM permanent magnet technology. Its ECM performance is equivalent to the legendary 007 and is ideal for open loop potable hot water systems with up to 500 feet of recirculation piping.
  • Page 9: Installation

    INSTALLATION: WARNING: Follow all local plumbing and electrical codes when installing this product. AVERTISSEMENT: Respectez tous les codes de plomberie et d’électricité locaux lors de l’installation de ce produit. CAUTION: To ensure all plumbing system components are protected from the damaging effects of water hammer, be sure an approved water hammer arrestor is installed in the system per locally recognized National plumbing codes.
  • Page 10 Figure 2: Typical Installation for Hot Water Recirculation Systems Water Heater Recommended Purging Steps: 1. Open fixture at highest point in system Open all isolation valves Once system is filled, close the fixture at the highest point in the system Close isolation valve on pump discharge (Option No.
  • Page 11 Figure 3: Typical Installation for Zoned Hydronic Heating Systems Boiler Supply (Option No. 1) Boiler Return (Option No. 2) Key: V1, V2, V3 = Shut-off Isolation Valve P = Taco circulator with IFC installed FF = Fast Fill Boiler Feed Valve PV4 = Purge Valve Recommended Purging Steps: 1.
  • Page 12 1. Location: The circulator can be installed on the supply or return side of the water heater or heat source. See Figures 2 & 3 on pages 3 and 4 for preferred locations. 2. Mounting Position: Circulator must be mounted with the motor in the horizontal position. See diagrams below for acceptable motor mounting orientations.
  • Page 13 WARNING: Use supply wires suitable for 90°C. AVERTISSEMENT: Employer des fils d’alimentation adeqauts pour 90°C. WARNING: Disconnect power when servicing. AVERTISSEMENT: Couper l’alimentation lors de l’entretien. CAUTION: Use flexible conduit only. Not for use with rigid conduit. AVERTISSEMENT: N’utiliser que du conduit flexible ; n’est pas fait pour du conduit rigide. WARNING: SERVICING OF DOUBLE-INSULATED APPLIANCES.
  • Page 14 007e Performance Curves 007e Performance Curves Orange LED Green LED Normal Mode Proportional Pressure Mode Green Mode...
  • Page 15 8. Troubleshooting the error codes: Listed below are potential diagnostic error codes which will appear on the LED display in case of a malfunction. FAULTS CONTROL PANEL CAUSES REMEDIES Increase the system suction Suction pressure is pressure within the LED on insufficient —...
  • Page 16: Replacement Parts

    REPLACEMENT PARTS Part# Description 198-213 RP Casing O-ring 198-214 RP Wiring plug connector (green) 198-215 RP Terminal box cover (black) 198-217 RP Terminal box cover screws (5 per bag) 0010-025 RP Integral Flow Check (IFC®) 007-007 RP Flange Gasket Kit Lead-Free Shut-Off FLANGE (SOLD SEPARATELY)
  • Page 17 NOTES -10-...
  • Page 18 NOTES -11-...
  • Page 19: Limited Warranty Statement

    LIMITED WARRANTY STATEMENT Taco, Inc. will repair or replace without charge (at the substance is suitable for use with a Taco product or TACO WILL NOT BE LIABLE FOR ANY SPECIAL IN- LIMITED WARRANTY STATEMENT CIDENTAL, INDIRECT OR CONSEQUENTIAL DAM- company’...

This manual is also suitable for:

007e-2f2007e-2f4

Table of Contents