Taco Comfort Solutions 00e VT2218 Series Instruction Sheet

Taco Comfort Solutions 00e VT2218 Series Instruction Sheet

Delta-t variable speed, ecm high-efficiency circulator

Advertisement

Quick Links

Delta-T Variable Speed, ECM High-Efficiency Circulator
SUPERSEDES: NEW
Plant ID No. 001-4267

DESCRIPTION:

The 00e
series VT2218 circulator is a temperature sensing, self-adjusting, variable speed
wet rotor circulator with an ECM, permanent magnet motor. Operating modes include
Delta-T, constant speed, set point heat, set point cool, and boiler protection. Its high
efficiency motor reduces power consumption by up to 85% compared to equivalent AC
permanent split capacitor circulators.

APPLICATION:

• Maximum operating pressure: 125 psi (862 kPa)
• Minimum water temperature: 36ºF (2ºC)
• Maximum water temperature: 230°F (110ºC)
• Electrical specifications:
Voltage: 110-120V, 50/60 Hz, single phase
Maximum operating power: 58W
Maximum amp rating: 0.67
• Equipped with a cast iron casing and should be used for closed loop systems only.
• Taco circulator pumps are for indoor use only – employer uniquement a l'interieur.
• Acceptable for use with water or maximum of 50% water/glycol solution.

FEATURES:

• 5 operating modes:
- Delta-T - variable speed, maintains constant ∆T, provides exact GPM flow required
- Constant Speed - 4 fixed speeds, maintains constant flow for zoning
- Set Point Heat - variable speed with boiler protection option, decreases speed on temperature rise
- Set Point Cool - variable speed, increases speed on temperature rise
- Boiler Protection - protects boiler from low return temperature and flue gas condensation
• Illuminated LCD displays:
- Operating mode, speed or temperature setting, watts, gpm, supply temperature, return temperature, and
error code diagnostics.
• Use with a Taco ZVC Zone Valve Control or SR Switching Relay for ON/OFF operation.
• Integral Flow Check (IFC) is included in carton. Simply press into discharge flange if required.
• Nut capture feature on flanges for easier fit up.
• Whisper quiet operation.
• BIO Barrier
protects the pump from system contaminants.
®
• SureStart automatic unblocking mode.
• Optional, 2-way flange model available to reduce SKU's and provide universal fit-up to any flange position.

INSTALLATION:

WARNING: Do not use in swimming pool or spa areas. Pump has not been investigated for these applications.
AVERTISSEMENT: Ne pas utiliser dans une piscine ou un spa. La pompe n'a pas été étudiée pour ces applications.
CAUTION: The addition of petroleum based fluids or certain chemical additives to systems using TACO equipment voids the
warranty. Consult factory for fluid compatibility.
ATTENTION: L'ajout de liquides à base de pétrole ou de certains additifs chimiques à des systèmes utilisant un équipement TACO
annule la garantie. Consultez le fabricant pour connaître la compatibilité de liquides.
CAUTION: Installations at elevations over 5000 feet must have higher fill pressure of 20 psi minimum to prevent pump cavitation
and flashing. Premature failure may result. Adjust expansion tank pressure to equal fill pressure. A larger size expansion tank may
be required.
ATTENTION: Des installations à des altitudes de plus de 1600 mètres doivent présenter une pression de remplissage plus élevée
de 20 psi au minimum afin d'éviter toute cavitation ou flashing de la pompe. Une défaillance prématurée peut en résulter. Réglez
la pression du réservoir d'expansion de façon qu'elle soit égale à la pression de remplissage. Un réservoir d'expansion d'une taille
supérieure peut être nécessaire.
00e
series VT2218
Instruction Sheet
102-510
Use for pumps with
date code TBD
or after
.
EFFECTIVE: June 14, 2016
For more information, visit
www.TacoComfort.com

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 00e VT2218 Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Taco Comfort Solutions 00e VT2218 Series

  • Page 1 series VT2218 102-510 Instruction Sheet ™ Use for pumps with date code TBD or after Delta-T Variable Speed, ECM High-Efficiency Circulator SUPERSEDES: NEW EFFECTIVE: June 14, 2016 Plant ID No. 001-4267 DESCRIPTION: The 00e series VT2218 circulator is a temperature sensing, self-adjusting, variable speed ™...
  • Page 2 KEY: VI, V2, V3 = SHUT-OFF ISOLATION VALVE P = TACO CIRCULATOR WITH IFC FF = FAST FILL BOILER FEED VALVE PV4 = PURGE VALVE RECOMMENDED PURGING STEPS: 1. CLOSE V1, PV4, V2 2. OPEN V3 3. OPEN FF VALVE 4.
  • Page 3 KEY: VI, V2, V3 = SHUT-OFF ISOLATION VALVE P = TACO CIRCULATOR WITHOUT IFC INSTALLED FF = FAST FILL BOILER FEED VALVE PV4 = PURGE VALVE ZV = ZONE VALVE RECOMMENDED PURGING STEPS: 1. CLOSE V1, PV4, V2 2. OPEN V3 AND ZV3 3.
  • Page 4 Typical Variable Speed Applications: Across a Series Supply • Delta-T Sensor Loop System Using - Varies speed to maintain Zone Valves a constant temperature Return Sensor differential (∆T) Outdoor Sensor Supply Across Multi-Zone Sensor Radiant Manifolds with Loop Actuators Return Boiler Sensor Sensor...
  • Page 5 CAUTION: To reduce the possibility of noise transmission, be sure to add vibration dampeners to piping when mounting circulator to wall or floor joists. ATTENTION: Pour réduire la possibilité de transmission de bruit, veillez à ajouter des amortisseurs de vibration à la tuyauterie lors du montage du circulateur sur des chevêtres de mur ou de plancher.
  • Page 6 To change operating mode and settings: a. Press and hold the SET button for 3 seconds until the operating mode on the LCD begins to flash. b. Use the UP or DOWN buttons to scroll through the 5 operating mode options. When the desired mode flashes on the LCD, press the SET button.
  • Page 7 Troubleshooting the error codes: ure tart Feature: The VT2218 is programmed with an automatic unblocking feature. In the case of a locked rotor condition, it will attempt to unblock the rotor with a series of rapid oscillating actions. It will repeat this process up to 100 times. If still locked after 100 attempts, “LOCKED ROTOR”...
  • Page 8 VT2218 PERFORMANCE CURVES SHADED AREA IS VARIABLE SPEED OPERATING RANGE LIMITED WARRANTY STATEMENT Taco, Inc. will repair or replace without charge (at If in doubt as to whether a particular substance the company’s option) any Taco High Efficiency is suitable for use with a Taco product or part, or ALL OTHER WARRANTIES, EXPRESS OR circulator or circulator part which is proven defec- for any application restrictions, consult the...

This manual is also suitable for:

00e vt2218-hy2-4c1a0000e vt2218-hy2-fc1a00

Table of Contents