Dryer Enclosure Requirements - ADC AD-50 Installation Manual

Phase 5 / dual timer
Hide thumbs Also See for AD-50:
Table of Contents

Advertisement

C. DRYER ENCLOSURE REQUIREMENTS
Bulkheads and partitions should be made of noncombustible materials and must be located a minimum of
12-inches (30.48 cm) above the dryer's outer top; 18-inches (45.72 cm) for steam dryers, except along the front
of the dryer which may be closed if desired.
NOTE: Allowances must be made for opening the control door.
X = 12-inch (30.48 cm) minimum, 24-inches (60.96 cm) is suggested for ease of maintenance.
* 1-inch (2.54 cm) maximum for electric dryers.
** 18-inch (45.72 cm) minimum for steam dryers.
NOTE: Air considerations are important for proper and efficient operation.
Dryers may be positioned sidewall to sidewall. However, a 1/16-inch (1.5875 mm) minimum allowance must be
made for opening and closing of the control door and the lint door. It is suggested that the dryer be positioned
about 2 feet (0.61 meters) away from the nearest obstruction for ease of installation, maintenance, and service
(to be measured from the back guard). Refer to the illustration above for details.
113066 - 17
www.adclaundry.com
11

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ad-50dr

Table of Contents