S+S Regeltechnik RYMASKON 500 - BACnet Operating Instructions Manual

S+S Regeltechnik RYMASKON 500 - BACnet Operating Instructions Manual

Room control unit with colour touch screen, with bacnet or modbus connection thermostat for controlling and regulating temperature, light, air conditioning and blind

Advertisement

Quick Links

D
MOD6.201 | Rev. 2022 - V12 DE | 17. 05. 2022
Operating instructions
RYMASKON
RYMASKON
Room control unit with colour touch screen,
with BACnet or Modbus connection
Thermostat for controlling and regulating
temperature, light, air conditioning and blind (1 zone)
S+S REGELTECHNIK GMBH | THURN-UND -TA XIS - STR. 22 | D -90411 NÜRNBERG | GERMANY | FON +49   ( 0 )  911 51947- 0 | w w w.S  p lusS.de
®
500 - BACnet
®
500 - Modbus

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the RYMASKON 500 - BACnet and is the answer not in the manual?

Questions and answers

Summary of Contents for S+S Regeltechnik RYMASKON 500 - BACnet

  • Page 1 (1 zone) S+S REGELTECHNIK GMBH | THURN-UND -TA XIS - STR. 22 | D -90411 NÜRNBERG | GERMANY | FON +49   ( 0 )  911 51947- 0 | w w w.S  p lusS.de...
  • Page 2: Installation And Commissioning

    - In cases of complaint, we will only accept complete units returned in their original packaging. S+S REGELTECHNIK GMBH | THURN-UND -TA XIS - STR. 22 | D -90411 NÜRNBERG | GERMANY | FON +49   ( 0 )  911 51947- 0 | w w w.S  p lusS.de...
  • Page 3: Installation

    An existing configuration can be transferred to other units using the RYMASKON USB-CT configuration tool (see next page). S+S REGELTECHNIK GMBH | THURN-UND -TA XIS - STR. 22 | D -90411 NÜRNBERG | GERMANY | FON +49   ( 0 )  911 51947- 0 | w w w.S  p lusS.de...
  • Page 4: Key Features

    • Operating modes Comfort (Normal), OFF, Boost, ECO, Holiday, Frost Protection S+S REGELTECHNIK GMBH | THURN-UND -TA XIS - STR. 22 | D -90411 NÜRNBERG | GERMANY | FON +49   ( 0 )  911 51947- 0 | w w w.S  p lusS.de...
  • Page 5: Technical Data

    EN 61000-6-1/3, EN 60730-1, EN 6100-4-2/4/5/11 S+S REGELTECHNIK GMBH | THURN-UND -TA XIS - STR. 22 | D -90411 NÜRNBERG | GERMANY | FON +49   ( 0 )  911 51947- 0 | w w w.S  p lusS.de...
  • Page 6 1 9 01 - 5 1 Z 3 - 0 00 2 - 0 0 0 units in the building S+S REGELTECHNIK GMBH | THURN-UND -TA XIS - STR. 22 | D -90411 NÜRNBERG | GERMANY | FON +49   ( 0 )  911 51947- 0 | w w w.S  p lusS.de...
  • Page 7: Dimensional Drawing

    B– RS485 B– (internally linked with 0V Supply) S+S REGELTECHNIK GMBH | THURN-UND -TA XIS - STR. 22 | D -90411 NÜRNBERG | GERMANY | FON +49   ( 0 )  911 51947- 0 | w w w.S  p lusS.de...
  • Page 8: User Interface

    During reset (dark screen), swipe in the direction of all four edges of the display and then follow the instructions. Confirm recalibration with “OK”. S+S REGELTECHNIK GMBH | THURN-UND -TA XIS - STR. 22 | D -90411 NÜRNBERG | GERMANY | FON +49   ( 0 )  911 51947- 0 | w w w.S  p lusS.de...
  • Page 9 (OPEN/CLOSE and the slats’ angle of inclination), if enabled. S+S REGELTECHNIK GMBH | THURN-UND -TA XIS - STR. 22 | D -90411 NÜRNBERG | GERMANY | FON +49   ( 0 )  911 51947- 0 | w w w.S  p lusS.de...
  • Page 10: Temperature Measurement

    • In OFF MODE, the target temperature is switched over to the frost protection setpoint. S+S REGELTECHNIK GMBH | THURN-UND -TA XIS - STR. 22 | D -90411 NÜRNBERG | GERMANY | FON +49   ( 0 )  911 51947- 0 | w w w.S  p lusS.de...
  • Page 11 If both RI1 and RI2 are configured as an outside temperature input, RI2 has priority. S+S REGELTECHNIK GMBH | THURN-UND -TA XIS - STR. 22 | D -90411 NÜRNBERG | GERMANY | FON +49   ( 0 )  911 51947- 0 | w w w.S  p lusS.de...
  • Page 12 The RH value can be accessed as a variable via the bus. S+S REGELTECHNIK GMBH | THURN-UND -TA XIS - STR. 22 | D -90411 NÜRNBERG | GERMANY | FON +49   ( 0 )  911 51947- 0 | w w w.S  p lusS.de...
  • Page 13: Off Mode

    (mode active) TAPPING THE ICON CANCELS THE MODE S+S REGELTECHNIK GMBH | THURN-UND -TA XIS - STR. 22 | D -90411 NÜRNBERG | GERMANY | FON +49   ( 0 )  911 51947- 0 | w w w.S  p lusS.de...
  • Page 14: Temperature Unit

    Fig. 7a Temperature in °C Fig. 7b Temperature in °F S+S REGELTECHNIK GMBH | THURN-UND -TA XIS - STR. 22 | D -90411 NÜRNBERG | GERMANY | FON +49   ( 0 )  911 51947- 0 | w w w.S  p lusS.de...
  • Page 15: Language Selection

    (opens by tapping the selection of the language options) S+S REGELTECHNIK GMBH | THURN-UND -TA XIS - STR. 22 | D -90411 NÜRNBERG | GERMANY | FON +49   ( 0 )  911 51947- 0 | w w w.S  p lusS.de...
  • Page 16 All possible configurations are displayed in Fig. 9a - 9e. S+S REGELTECHNIK GMBH | THURN-UND -TA XIS - STR. 22 | D -90411 NÜRNBERG | GERMANY | FON +49   ( 0 )  911 51947- 0 | w w w.S  p lusS.de...
  • Page 17 S+S REGELTECHNIK GMBH | THURN-UND -TA XIS - STR. 22 | D -90411 NÜRNBERG | GERMANY | FON +49   ( 0 )  911 51947- 0 | w w w.S  p lusS.de...
  • Page 18 • Gearwheel icon to open setting mode (see “Parameter configuration”). S+S REGELTECHNIK GMBH | THURN-UND -TA XIS - STR. 22 | D -90411 NÜRNBERG | GERMANY | FON +49   ( 0 )  911 51947- 0 | w w w.S  p lusS.de...
  • Page 19: Alarm Display

    No input ▯ – – – – – – S+S REGELTECHNIK GMBH | THURN-UND -TA XIS - STR. 22 | D -90411 NÜRNBERG | GERMANY | FON +49   ( 0 )  911 51947- 0 | w w w.S  p lusS.de...
  • Page 20: Holiday Mode

    Fig. 15c Holiday OFF display Fig. 15d Holiday ECO display S+S REGELTECHNIK GMBH | THURN-UND -TA XIS - STR. 22 | D -90411 NÜRNBERG | GERMANY | FON +49   ( 0 )  911 51947- 0 | w w w.S  p lusS.de...
  • Page 21: Parameter Configuration

    S+S REGELTECHNIK GMBH | THURN-UND -TA XIS - STR. 22 | D -90411 NÜRNBERG | GERMANY | FON +49   ( 0 )  911 51947- 0 | w w w.S  p lusS.de...
  • Page 22: Parameter Table

    OFF to standard mode 1 = Disabled S+S REGELTECHNIK GMBH | THURN-UND -TA XIS - STR. 22 | D -90411 NÜRNBERG | GERMANY | FON +49   ( 0 )  911 51947- 0 | w w w.S  p lusS.de...
  • Page 23: Operating Modes

    S+S REGELTECHNIK GMBH | THURN-UND -TA XIS - STR. 22 | D -90411 NÜRNBERG | GERMANY | FON +49   ( 0 )  911 51947- 0 | w w w.S  p lusS.de...
  • Page 24 Unit change via 1 = Enabled home screen (°C/°F) S+S REGELTECHNIK GMBH | THURN-UND -TA XIS - STR. 22 | D -90411 NÜRNBERG | GERMANY | FON +49   ( 0 )  911 51947- 0 | w w w.S  p lusS.de...
  • Page 25 0000 to 9999 (default 0000) (for 0000: no PIN required) S+S REGELTECHNIK GMBH | THURN-UND -TA XIS - STR. 22 | D -90411 NÜRNBERG | GERMANY | FON +49   ( 0 )  911 51947- 0 | w w w.S  p lusS.de...
  • Page 26 1 = On Version Software version x.xx (Modbus/BACnet) S+S REGELTECHNIK GMBH | THURN-UND -TA XIS - STR. 22 | D -90411 NÜRNBERG | GERMANY | FON +49   ( 0 )  911 51947- 0 | w w w.S  p lusS.de...
  • Page 27 500 - BACnet RYMASKON ® 500 - Modbus S+S REGELTECHNIK GMBH | THURN-UND -TA XIS - STR. 22 | D -90411 NÜRNBERG | GERMANY | FON +49   ( 0 )  911 51947- 0 | w w w.S  p lusS.de...
  • Page 28 Schutzrechte sind zu berücksichtigen. Einwandfreie Qualität gewährleisten wir im Rahmen unserer Allgemeinen Lieferbedingungen. S+S REGELTECHNIK GMBH | THURN-UND -TA XIS - STR. 22 | D -90411 NÜRNBERG | GERMANY | FON +49   ( 0 )  911 51947- 0 | w w w.S  p lusS.de...