Temperature Measurement; Main Control Circuit - S+S Regeltechnik RYMASKON 500 - BACnet Operating Instructions Manual

Room control unit with colour touch screen, with bacnet or modbus connection thermostat for controlling and regulating temperature, light, air conditioning and blind
Table of Contents

Advertisement

Operating instructions
RYMASKON
®
500 - BACnet
RYMASKON
®
500 - Modbus
TEMPERATURE
MEASUREMENT
Sensor assignment
and designations
of the temperature zone

MAIN CONTROL CIRCUIT

(Changeover)
Heating or cooling
S+S REGELTECHNIK GMBH | THURN-UND -TA XIS - STR. 22 | D -90411 NÜRNBERG | GERMANY | FON +49   ( 0 )  911 51947- 0 | w w w.S  p lusS.de
®
The RYMASKON
500 Thermostat can show up to three temperatures and the
relative humidity (RH option) in the grey action circle.
Room, zone 1, main control circuit
The room temperature is used together with the target temperature in the main
control circuit to regulate the temperature. The internal temperature sensor is
connected by default. Alternatively, an external temperature sensor (NTC10K)
connected to RI1 ⁄ RI2 can be used (Settings - Inputs - RI1 ⁄ RI2 Mode - Control).
The temperature value is always displayed and cannot be hidden. The name can be
changed (Settings - Display - Zone 1 Text).
Floor, zone 2, auxiliary control circuit, MIN - MAX
With the floor temperature, the temperature of a floor heating system can be
regulated via configurable temperature limits (min. limit/max. limit), for example.
The function and display is active if an external temperature sensor (NTC10K) is
connected to RI1 ⁄ RI2 and the connected channel is configured to "MIN - MAX"
(Settings - Inputs - RI1 ⁄ RI2 Mode - MIN-MAX).
The floor temperature is shown in the action circle. The name can be changed
(Settings - Display - Zone 2 Text). If "Zone 2 Text" is configured to disabled,
the temperature is not displayed.
Outside, zone 3, simple display
The outside temperature is displayed in the action circle if an external temperature
sensor (NTC10K) is connected to RI1 ⁄ RI2 and the connected channel is configured to
"Outside" (Settings - Inputs - RI1 ⁄ RI2 Mode - Outside). Alternatively, the unit can be
configured so that the outside temperature is transmitted via the bus to the unit
(Settings - Inputs - outside temperature source - network).
The name can be changed (Settings - Display - Zone 3 Text).
If "Zone 3 Text" is configured to disabled, the temperature is not displayed.
NOTE:
For explanations regarding RI1 ⁄ RI2 see chapter MODES FOR INPUTS RI1 & RI2
For explanations regarding Auxiliary control circuit (floor) see chapter
AUXILIARY CONTROL CIRCUIT
The thermostat regulates the target temperature through the switching on and off of the relay, as required. In
this process, a hysteresis in the control program causes – in heating mode, for example – the target temperature
and the hysteresis to require being exceeded before the relay switches off. In cooling mode, the hysteresis
functions the other way around. This prevents switching on or off too quickly. The diagram below illustrates this
principle. The main temperature control circuit can be forcibly changed via the bus or through the digital input
(DI1) to heating or cooling mode (changeover). This makes it possible to use the same pipe for heating and cooling
in different seasons (summer/winter mode).
HEATING
ON
OFF
-
HYS
HYS = Hysteresis
e.g. 1.0°C / 1.8°F
TARGET
SETPOINT e.g 21°C / 69°F
The target temperature can be adjusted by the user using the arrow keys UP and DOWN and it
changes depending on the operating conditions:
• In COMFORT MODE (standard mode), the target temperature (room)
can be adjusted by the user or via the bus.
• In ECO MODE, the target temperature is switched over to the ECO setpoint.
• In OFF MODE, the target temperature is switched over to the frost protection setpoint.
ON
Target
Temperature
OFF
+
HYS = Hysteresis
e.g. 1.0°C / 1.8°F
10
COOLING
Target
Temperature
-
HYS
TARGET
SETPOINT e.g 22°C / 71°F
Room
20
°C
.1
Floor
20
°C
.1
Outside
10
°C
.5
+

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rymaskon 500 - modbus

Table of Contents