Operating instructions
RYMASKON 500 Series | Parameter Table | Last Updated: 16/05/2022 (EN)
RYMASKON
®
500 - BACnet
RYMASKON
®
500 - Modbus
PARAMETER TABLE
Setting mode via unit screen
PARAMETER-TABELLE
Einstellungsmodus über Gerätebildschirm
CONTROL SETTINGS
Parameter name
Nominal setpoint
ECO heating setpoint
ECO cooling setpoint
Frost setpoint
Min. setpoint adj.
Max. setpoint adj.
Hysteresis
Control type
Min. limit
Max. limit
Hysteresis limit
Reset setpoint
S+S REGELTECHNIK GMBH | THURN-UND -TA XIS - STR. 22 | D -90411 NÜRNBERG | GERMANY | FON +49 ( 0 ) 911 51947- 0 | w w w.S p lusS.de
Description
Nominal target temperature
ECO heating target temperature
ECO cooling target temperature
Frost protection target temperature (OFF mode)
Lowest configurable target temperature
Highest configurable target temperature
Hysteresis of the temperature main control circuit
Heating and / or cooling control of the temperature main
control circuit (cf. section main control circuit)
NOTE:
The changeover function is activated with
value 2 (heating / cooling). Switchover
between heating and cooling mode occurs via
the digital input or via the bus.
Lower limit value for floor heating
(Cf. section Auxiliary control circuit)
Upper limit value for floor heating
(Cf. section Auxiliary control circuit)
Hysteresis limit value for floor heating control
(Cf. section Auxiliary control circuit)
Reset of the target temperature to the nominal setpoint
upon switchover from OFF to standard mode
Range
0.0 to 95.0 °C/°F (default 21.0°C)
0.0 to 95.0 °C/°F (default 19.0 °C)
0.0 to 95.0 °C/°F (default 24.0 °C)
0.0 to 95.0 °C/°F (default 8.0 °C)
0.0 to 95°C/°F (default 14.0)
0.0 to 95°C/°F (default 30.0)
0.0 to 20.0 °C/°F (default 1.0°C)
0 = Heating (default)
1 = Cooling
2 = Heating / cooling
0.0 to 95.0 °C/°F (default 18.0 °C)
0.0 to 122.0°C/°F (default 30.0 °C)
0.0 to 10.0 (default 1.0)
0 = Enabled (default)
1 = Disabled