Toshiba GR200 Series Instruction Manual page 491

Hide thumbs Also See for GR200 Series:

Advertisement

Select logics for SBO/DIR modes
3.7.2
The user should set scheme switch [GCNT01-EN] to On prior to counting.
Receiving "Select command Reset" from the remote-end
(i)
Figure 3.7-5 outlines the reception of the Select command 'Reset' from the remote-end.
Wait for a command
Select stage
Select command Reset from the remote-end
Signal
reception
IEC61850
Figure 3.7-5 Outline of Select command 'Reset'
Input point required mapping
Figure 3.7-6 shows the select logic when a "Select command Reset (Remote-Reset-Control)"
signal is applied to the GCNT01 function. The logic has an input-point "GCNT01_CMM_REQ"
for the reception of the select command. That is, the input-point must be mapped for IEC61850
communication. The function will fail to operate if mapping is not performed correctly. We will
discuss how to map the input-points for IEC61850 communication in section 3.7.5.
Output signal to BO
The
GCNT01
function
"GCNT01_SLD_CSCN", when the GCNT01 function determines that the input signal
"Remote-Reset-Control" is true. If the GCNT01 function determines that the "Remote-Reset-
Control" is not true, the GCNTS01 function returns to the "Wait for a command" stage.
Failed
Select
Select logic
decision
Success
can
issue
a
- 470 -
Wait for a next command
Cancel logic
Cancel command
Signal output
Cancel logic
Operate logic
Operate command
Operate logic
"Complete"
signal
6F2S1915 (0.46)
at
the
output
point
GRZ200 (Soft 031 & 032)