Toshiba GR200 Series Instruction Manual page 441

Hide thumbs Also See for GR200 Series:

Advertisement

Setting
2.27.7
PROT_COMMON (Function ID: 48A001)
Setting items
UVLS
UVLG
OCD
CB
CB-System
CB1-Contact
CB2-Contact
TCBLOSPH
CB-SV
TCBSV
DS
DS-Contact
DS-SV
TDSSV
DL
DLDbyUV
DLDbyCB
TDLD
UserLogicSW1
UserLogicSW2
UserLogicSW3
UserLogicSW4
Range
Unit
1A rating
5A rating
5.0 - 130.0
V UV phase-phase relay operating value
5.0 - 130.0
V UV phase-ground relay operating value
0.05 -
0.25 -
A OCD relay operating value
0.20
1.00
1CB / 2CB
- Single CB or One-and-a-half CB system
NO / NC / Both
- Kind of injected CB contact
NO / NC / Both
- Kind of injected CB2 contact
0.00 - 0.10
s CB loss phase time
Off / On
- CB contact supervisor enable
0 - 100
s CB contact supervisor time
NO / NC / Both
- Kind of injected DS contact
Off / On
- DS contact supervisor enable
0 - 100
s DS contact supervisor time
Off / On
- Dead line detection by under voltage
Off / On
- Dead line detection by CB open
0.00 - 300.00
s Dead line detection timer
S1 / S2 / S3
- User Logic Switch for General purpose
S1 / S2 / S3
- User Logic Switch for General purpose
S1 / S2 / S3
- User Logic Switch for General purpose
S1 / S2 / S3
- User Logic Switch for General purpose
- 420 -
6F2S1915 (0.46)
Contents
GRZ200 (Soft 031 & 032)
Default
Note
1A
5A
77.0
45.0
0.10
0.50
1CB
NO
NO
0.03
Off
10
NO
Off
60
Off
Off
10.00
S1
S1
S1
S1