Installation Regulations For Electrical Installations With Residual Current Protective Devices - Siemens SENTRON Manual

Hide thumbs Also See for SENTRON:
Table of Contents

Advertisement

9.4
Installation regulations for electrical installations with residual
current protective devices
Standard
Application
(DIN VDE ...
or BGI ...)
0100-410
Protection against electric
shock
Socket outlets up to 20 A,
outdoor installations
0100-482
Fire protection for partic-
ular risks or safety hazards
0100-701
Rooms with baths or
showers,
socket outlets in zone 3
0100-702
Pools in swimming baths
and other pools
0100-703
Rooms and cabins with
sauna heating systems
0100-704
Construction sites,
and
Socket outlet circuits up to
BGI 608
32 A and for hand-held
tools, plugs and sockets
I
> 32 A
n
0100-705
Agricultural and horti-
cultural, general, socket
outlet circuits
0100-706
Conductive areas with
limited freedom of move-
ment, fixed equipment
0100-708
Electrical installations
on camping sites, fixed
feeding points for every
socket outlet and every
final circuit
0100-710
Medical premises with a
TN-S system, depending
on application group
1 or 2 and equipment
0100-712
Solar PV power supply
systems (without simple
isolation)
Required I
Recommended Siemens RCCB
Δn
[mA]
(taking into consideration the pos-
sible nature of the residual currents
in the equipment)
Type A Type F SIQUENCE
30 ... 500
+
10 ... 30
+
30 and 300
+
10 ... 30
+
10 ... 30
+
10 ... 30
+
≤ 30 mA
+
≤ 500 mA
+
≤ 300
+
10 ... 30
+
10 ... 30
+
10 ... 30
+
10 ... 30 or
+
≤ 300
+
≤ 300
SIGRES
Type B/B+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
85