Replacing cable with one of different Ampere capacity

• If cable to EV is being replaced or changed.
• Determine new cable and connector rating.
• Note: Rating is normally printed on the side of the cable & connector.
• Determine Branch Circuit Protection rating.
• Look up cable and breaker amps in table below to find the dial position number or
letter.
• Set Dial position per below (see "Set Dial Position")
Minimum Cord set
rating
12
16
20
24
32
40
48
56
63
72
80
Has not been set — Original Position from Factory
All values in amperes
US NEC Breaker Size
15
20
25
30
40
50
60
70
80
90
100
Reserved
Reserved
Reserved
Reserved
Page 6 | Doc #: NU-000032-A, PowerPort Installation & Setup
UK/EU Breaker Size
13
16
20
25
32
40
50
-
63
-
80
Dial Position
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F