is connected correctly. See section 2.2 for help with connecting your
alarm cable.
To enable the relay test, scroll to RLY TEST DISABLED, press the MENU
button, and the screen will display RLY TEST ENABLED.
Press the UP button to scroll to RELAY A INACTIVE. To activate the test,
press the MENU button and the screen will change to RELAY A ACTIVE.
Your connection for relay A (Major Alarm by default) should now be in
alarm. If it is not, check your connections to make sure you have your
cable connected properly. If problems persist call the Valere technical
support line (1-866-240-6614). Press the MENU button again to change
back to RELAY A INACTIVE. Press the UP button to move to the next
relay and repeat the above instructions for relays B through F.
Once all relays have been tested and verified, press the DN button to
scroll back to relay A. As you scroll through the relays verify that all the
relays are inactive. If you leave a relay active the alarm will be in a
constant alarm state.
Press the UP button to move to the next setpoint or scroll to EXIT TESTS
and press MENU.
7.6

Thermal

The thermal menu allows you to set up thermal compensation for your
batteries. An Admin login is required to enable or adjust any values. If
thermal compensation is disabled the different setpoints will not be visible in
either the review or configuration menu. See battery manufacturer's
documentation for information on required thermal settings for your battery
type.
This menu can be accessed by pressing the MENU button at the CONFIG
THERMAL menu. The first setpoint displayed will be T COMP DISABLED.
Press the UP button to continue scrolling thru the thermal menu. The menu
will circle back to T COMP DISABLED once the end has been reached.
To exit this menu press the UP button until EXIT THERMAL is displayed on
the screen, and press MENU to exit. This will take you back to the
configuration menu. Continue to the next menu for adjustment or follow the
exit instructions at the beginning of this section to exit.