then be adjusted by pressing the UP and DN buttons in the corresponding
directions. This value can be adjusted in .05 V increments. Once the
desired value is reached, press the MENU button to accept the new value.
This value must be less than the 1 < HVSD setpoint and greater than the
LVD OPEN setpoint.
Press the UP button to move to the next setpoint or scroll to EXIT
SETPOINTS and press MENU.
7.4

Alarms

The alarms menu allows you to adjust controller alarm setpoints such as high
voltage shutdown, high voltage alarm, battery on discharge alarm, capacity
alarm, current share alarm, and communication fail alarm.
This menu can be accessed by pressing the MENU button at the CONFIG
ALARMS menu. The first alarm displayed will be the high voltage shutdown
(HVSD) of the system. Press the UP button to continue scrolling thru the
alarm menu. The menu will circle back to HVSD once the end has been
reached.
To exit this menu press the UP button until EXIT ALARMS is displayed on
the screen, and press MENU to exit. This will take you back to the
configuration menu. Continue to the next menu for adjustment or follow the
exit instructions at the beginning of this section to exit.
Alarms
High Voltage Shutdown
High Voltage Alarm
Battery Discharge Alarm
Low Voltage Warning Alarm
Capacity Alarm
Current Share Alarm
Communication Failure Alarm
7.4.1 High Voltage Shutdown (HVSD)
HVSD is the DC voltage at which the rectifiers will shutdown if exceeded.
To adjust the high voltage shutdown, scroll to HVSD V = xx.xx, press the
MENU button, and the screen will display CHOOSE: V = xx.xx. The value
can then be adjusted by pressing the UP and DN buttons in the
corresponding directions. This value can be adjusted in 0.25 V
increments. This value must be at least 1V greater than the float voltage
value. Once the desired value is reached, press the MENU button to
accept the new value.
Page 17 of 47
DO600000191
12V (Volts)
11.50 - 15.00
11.50 - 15.00
10.00 - 13.50
9.00 - 13.00
enabled or disabled
enabled or disabled
enabled or disabled
enabled or disabled
enabled or disabled
enabled or disabled
Table 5 - Alarm value ranges
24V (Volts)
48V (Volts)
22.00 - 29.50
48.00 - 59.00
24.00 - 28.50
48.00 - 59.00
20.00 - 27.00
40.00 - 55.00
20.00 - 26.00
40.00 - 52.00
enabled or disabled
enabled or disabled
enabled or disabled
November, 2006
Version 2.0