Once the desired value is reached, press the MENU button to accept the
new value.
Press the UP button to move to the next setpoint or scroll to EXIT
ALARMS and press MENU.
7.4.5 Capacity Alarm (Capacity)
Capacity alarm is the alarm that is triggered when N+1 redundancy is lost.
This is your warning that the system will be on battery back up if another
rectifier is lost.
To enable the capacity alarm, scroll to CAPACITY DISABLED, press the
MENU button, and the screen will display CAPACITY ENABLED.
Press the UP button to move to the next setpoint or scroll to EXIT
ALARMS and press MENU.
7.4.6 Current Share Alarm (I-share)
Current share alarm is the alarm that is triggered when one or more
rectifier is not sharing the current evenly.
To enable the current share alarm, scroll to I-SHARE DISABLED, press
the MENU button, and the screen will display I-SHARE ENABLED.
Press the UP button to move to the next setpoint or scroll to EXIT
ALARMS and press MENU.
7.4.7 Communication Failure Alarm (Comm Fail)
Communication fail alarm is the alarm that is triggered when the controller
loses communication with a rectifier. This is caused by a rectifier being
removed from the system. This alarm can be cleared from the main menu
by pressing MENU when the screen reads HIT MENU TO CLEAR.
To enable the communication fail alarm, scroll to COMM FAIL DISABLED,
press the MENU button, and the screen will display COMM FAIL
ENABLED.
Press the UP button to move to the next setpoint or scroll to EXIT
ALARMS and press MENU.
7.5
Tests
The tests menu allows you to adjust controller test setpoints such as boost,
battery discharge test, and Relay test. All tests can be executed from the
Page 19 of 47
DO600000191
Version 2.0
November, 2006