2 Unscrew the screws (four PTT screws 4×25, indicated by
), and remove the motor (DC).
Assembly precaution
• Different types of motors (for SA fan and EA fan) are
provided for this product. When installing the motors,
be careful not to confuse between them.
• Different connector parts are used for the motors.
(
Motor (DC) (for SA fan): six-pin connector
Motor (DC) (for EA fan): seven-pin connector
Tightening torque:
1.1 ± 0.2 N . m
( 7 ) Remove the Lossnay core
1 Remove the fixing tapes for the sheet (two locations,
indicated by ).
2 Unscrew the screws (seven PTT screws 4×14, indicated
by ), and remove the fan casing (orifice) of the EA fan
assembly.
Precaution
Drain water may drip. Handle the fan casing (orifice)
with care.
Assembly precaution
If the fixing tapes cannot be affixed again, use commer-
cially available tapes to fix the sheet to the fan casing.
Tightening torque:
1.1 ± 0.2 N . m
3 Loosen the screws (two PTT screws 4×14, indicated by
), and turn the fix pieces by 90°.
Tightening torque:
1.1 ± 0.2 N . m
4 Take out the Lossnay core in the direction of the arrow.
Precaution
Dew condensation water may drip. Handle the Lossnay
core with care.
)
Sheet
EA side
─ 34 ─
Motor (DC)
Fan casing (Orifice)
Fix piece
SA side
Lossnay core