Daikin FWW Series Technical Manual page 19

Chilled water fan coil units
Hide thumbs Also See for FWW Series:
Table of Contents

Advertisement

Application Information
Ceiling Concealed Drain Piping Work
• The drain pipe must be installed as shown in the diagram (see diagram above) to avoid damage caused
by leaks and condensation.
• For the best result, keep the piping as short as possible. Slant the piping at an angle to improve the flow.
• Ensure the drain pipe is securely insulated.
• It is necessary to provide a drain trap in the drain outlet to relieve pressure that exists within the unit
compared to the outside atmospheric pressure when the unit is operating. The drain trap is to avoid
possibility of splashes or an odor.
• Keep pipes as straight as possible for easy cleaning and to prevent the accumulation of dirt and debris.
• Conduct a water drainage test after the installation is completed. Make sure that the drainage flow is
smooth.
• In humid environments, use an extra drain pan to cover the entire area of the indoor unit.
Insulate securely
Bottom of
the unit
Drain
trap
Unit : mm
Do not leave in water
15