EXTERNAL CONNECTIONS
Connect external connections on terminal blocks X28, X29
and X30 on the base board (AA2).
BT1 14
BT50 13
BT25 12
BT6 11
AUX8 10
AUX7 9
AUX6 8
AUX5 7
AUX4 6
AUX3 5
AUX2 4
AUX1 3
+5V 2
0-5V 1
-X28
Sensors
Outside sensor
The outdoor temperature sensor (BT1) is placed in the shade
on a wall facing north or north-west, so it is unaffected, for
example, by the morning sun.
Connect the outdoor temperature sensor to terminal block
AA2-X28:14 and AA2-X29:GND.
If a conduit is used it must be sealed to prevent condensa-
tion in the sensor capsule.
AA2-X28
BT1
14
BT50
13
BT25
12
BT6
11
AUX8
10
AA2-X29
Temperature sensor, hot water charging
The temperature sensor, hot water charging (BT6) is placed
in the submerged tube on the water heater.
Connect the sensor to terminal block AA2-X28:11 (or to one
of the selectable AUX inputs) and to terminal block AA2-
X29:GND.
Settings for hot water are made in menu 2 "Hot water".
AA2-X28
BT6
11
AUX8
10
AUX7
9
AUX6
8
AUX5
7
AA2-X29
NIBE S1155
AA2
X27
POWER
ERROR
12
BE3
INT COM
11
BE2
EXT COM
CPU
10
BE1
PWM1
9
GND
PWM0
X30
8
+5V
7
0-5V
6
OT−
5
OT+
4
A
3
B
X29
2
+12V
1
GND
-X29
-X30
X28
BT1
BT6
Temperature sensor, hot water top
A temperature sensor for hot water top (BT7) can be connec-
ted to S1155 to show the water temperature at the top of
the tank (if it is possible to install a sensor at the top of the
tank).
Connect the sensor to terminal block X28:10 (or to one of
the other selectable AUX inputs) and to terminal block AA2-
X29:GND.
AA2-X28
BT7
AUX8
10
AUX7
9
AUX6
8
AUX5
7
6
AUX4
AA2-X29
External supply temperature sensor
If an external supply temperature sensor (BT25) needs to
be used, connect it to terminal block AA2-X28:12 and to
terminal block AA2-X29:GND.
AA2-X28
BT1
14
BT50
13
BT25
12
BT6
11
AUX8
10
AA2-X29
Chapter 5 | Electrical connections
BT25
23