Safety Advice; Unit Identification - Carrier 50HB Manual

Horizontal package air conditioners
Table of Contents

Advertisement

Horizontal package air conditionners
4. S
AFETY ADVICE
To avoid any risk of accident during installation, commissioning or
maintenance, it is obligatory to take into consideration the following
specifi cations for the units: refrigerated circuits under pressure, refrigerant
presence, electrical voltage presence and implantation place.
Because of all of this, only qualifi ed and experienced personnel can
perform maintenance tasks or unit repairs.
It is required to follow the recommendations and instructions
in the maintenance brochures, the labels, and the specifi c
instructions.
It is necessary to comply with the norms and regulations in
effect. It is recommended to consult the competent authorities
regarding the applicable regulations for users of units or
components under pressure. The characteristics of these units
or components are included on the plates of characteristics
or in the regulatory documentation provided with the product.
The compressor and line surfaces can reach temperatures
above 100ºC causing burns to the body. In the same fashion,
under certain conditions these surfaces can reach very cold
temperatures that can cause freezing risks.
Use safety goggles and gloves on the job. Be careful with
sharp parts or elements in the unit.
V-220005
Caution: Before intervening in the unit, verify that the main
power to the unit is cut off. An electric shock can cause
personal damage.
V-220004
Note: In order to recycle these units follow the stipulations
of Directive 2012/19/EU on Waste electrical and electronic
equipment (WEEE).
5. U
NIT IDENTIFICATION
Check the condition of the equipment upon delivery.
Check that the details on the label, the packing and the data plate match
the order. If equipment has been damaged, or there is a shortfall in
delivery, notify accordingly.
All units bear, legibly and indelibly, a data plate located in a prime space,
as appears in the attached image: Check that this plate matches the
correct model.
Año\An.Year
Ref\Reference
1
2
Producto\Product\Produit
Ref. Produit\Item Nbr
5
Tension\Voltage
Kit Elec.
8
Refrigerant
Refrig.KG (Fábrica\Factory\Usine)/Co2 Teq.
11
12
PSmax(AP\HP)
PSmax(BP\LP)
Temp. Max./ IP
13
14
CARRIER SCS
Fabricante\Fabricant\Manufacturer:
Route de Thil
Compañía Industrial de Aplicaciones Térmicas, S.A.
01122 Montluel-FRANCE
P. Ind. Llanos de Jarata s/n. 14550 Montilla-SPAIN
Contient des gaz à effet de serre fluorés \ Contains fluorinated greenhouse gases regulated by the Kyoto protocol
Contiene gases fluorados de efecto invernadero regulados por el protocolo de Kyoto
No Serie\serial Nbr.
3
4
6
7
Max.Intensidad\Intensité\Current
9
10
Peso\Poids\Weight
NoBo
15
16
Refrigerant leaks:
A periodical check must be performed for refrigerant gas leaks as
per Regulation (EC) Nº517/2014 over certain greenhouse effect
fl uoride gases. Please, consult the frequency of checks in chapter
of "Maintenance".
These units work with refrigerant gas
Components of the R-410A
Chemical formula
Weight ratio
Unitary global warming potential (GWP)
Global warming potential (GWP)
In case of a leak:
- Toxicity: According to ASHRAE 34, R-410A belongs to the A1/A1 group,
i.e. with high safety both in the mix and also in the case of a leak.
- Although it is not toxic, in case of a leak to atmospheric pressure the
liquid phase evaporates. The resulting vapours are heavier than air
and can displace the technician local air. In case of an accidental
discharge in a closed enclosure, fans must be used to eliminate said
vapours.
- Although the R-410A is not fl ammable, when in contact with a fl ame
o hot spot it can decompose in fl uorhydric acid HF and fl uophosgene
COF
highly toxic and corrosive.
2
- To detect leaks, an electronic leak detector, an ultraviolet lamp or
soapy water must be used. Flame detectors do not help.
Important: Immediately repair any refrigerant leak, using
a recovery unit specifi c for R-410A that avoids a possible
mixture of refrigerants and/or oils.
Legend
Year of manufacture
1
Commercial product name
2
Serial number
3
Description of the product
4
Purchase order number
5
Sales order number
6
Work order number
7
Power supply
8
Power output of the auxiliary electrical heaters kit (optional) (kW)
9
Maximum absorbed current under full load (A) ( including the electrical kit)
10
Type of refrigerant
11
Refrigerant content (kg) and Environment impact (CO
12
Maximum service pressure in the high pressure side (R-410A = 42 bar)
13
Maximum service pressure in the low pressure side (R-410A = 24 bar)
14
Maximum operating temperature (refer to "Opration limits")
15
Maximum shipment and storage temperature: +50ºC
Electrical protection rating: IP54
17
Operation weight (kg) (empty weight + fl uid + refrigerant)
16
Notifi ed Body number for surveillance of the Pressure Equipment Directive
17
Note: The serial number must be used in all correspondence
regarding the unit.
R-410A
.
R-32
R-125
CH2F2
CHF2CF3
50%
50%
675
3.500
2.088
Teq.)
2
5