FUNCTION AND OPERATION OF PROTECTIVE PROCEDURES
Function
NO
1
Indoor fan
Stops operation if no rotation pulse signal
lock
is input from the indoor fan motor for one
minute.
Indoor fan
Stops operation if the rotation pulse signal
rpm error
from the indoor fan indicates low rpm
(approximately 300 rpm or less).
2
Indoor
Lowers the operating frequency if the
freezing
temperature of the indoor heat exchanger
guard
goes below 5°C during cooling. Stops the
compressor if the temperature stays below
0°C for 4 minutes.
3
Indoor
Lowers the operating frequency if the
overheating
temperature of the indoor heat exchanger
control
rises above the overheating temperature
during heating. Stops the compressor if the
temperature stays above the overheating
temperature for 1 minute at minimum
frequency or less.
Set values for overheating temperature
During normal operation: 45°C to 54°C
During full power operation: 47°C to
58°C
4
DC
Stops the compressor if a current of
overcurrent
approximately 23A or more flows in the
power transistor module.
5
AC
Lowers the operating frequency if the
overcurrent
compressor AC current exceeds
set value( ).Show "2-2(1)AC peak
control"
Stops the compressor if the current
exceeds at 40Hz or less set value( ).
6
Compressor
Lowers the operating frequency if the
overheating
temperature of the compressor chamber
control
thermistor (TH1) rises above 105°C.
Stops the compressor if the thermistor
stays above 105°C for 1 minutes at
minimum frequency or less.
7
Compressor
Stops the compressor if the compressor
high
chamber thermistor is above 114°C.
temperature
(Or when TH1 shorts)
error
( )
Cool
6.2A
Set
value
6.7A
Heat
Operation
Description
When indoor
fan is rotating
During cooling
and dry
During heating
During
compressor
operation
During
compressor
operation
During
compressor
operation
During
operation
18
Detection
Restart
time
condition
Operation OFF
Automatically
restarts when the
exchange
temperature rises
above the freezing
prevention
temperature (above
2°C)
Automatically
restarts when the
exchange
temperature goes
below the
overheating
temperature.
Automatically
restarts after safety
time (170 seconds)
Automatically
restarts after safety
time (170 seconds)
Automatically
restarts after safety
time (170 seconds)
Automatically
restarts when
thermistor (TH1)
temperature falls
below 100°C
(approximately 30
minutes)
Self diagnostic
display
Restart
Indoor Outdoor
times
No limit
Yes
No
No limit
No
No
No limit
No
No
8times
Yes
Yes
4 times
Yes
Yes
No limit
No
No
4 times
Yes
Yes