Page 4
Declaration of Conformity (Manufacturer’s Declaration) Qingdao Hisense Hitachi Air-conditioning Systems Co., Ltd. Add: 218, Qianwangang Road, Economic & Technical Development Zone, Qingdao, P.R. China declares under its sole responsibility that the air conditioning models to which this declaration relates: RPI-16.0KFNQL, RPI-16.0KFNQH, RPI-20.0KFNQL, RPI-20.0KFNQH,...
Page 5
21~43 Heating Operation: -7~15 The indoor unit will stop when the temperature outside is lower than The indoor unit can be only used with the outdoor unit as follows. Indoor Unit Outdoor Unit RPI-16.0KFNQL RAS-16FSN1Q RPI-16.0KFNQH RPI-20.0KFNQL RPI-20.0KFNQH RAS-20FSN1Q RPI-20.0KFNQLF...
Page 6
Contact the Customer Care for more information. HITACHI...
Page 8
Do not install the indoor unit outdoor unit remote controlswitch and cable within approximately 3 meters from strong electromagnetic wave radiatoes such as medical equipment. Do not touch the exchanger to avoid being injured. Install the drain pipe according to the installation manual to make sure drain smoothly.Insulate the drain pipe to avoid Install the indoor unit on a foundtation firm...
Page 9
Refrigerant Gas Pipe Indoor unit Connection (A) Refrigerant Liquid Pipe Connection (B) MOD EL 16.0 20.0...
Page 11
(Including Two Remote Temperature Sensors)
Page 12
(unit:mm) Working Keep enough distance between the indoor unit and Space the walls around to avoid contaction each other Air Inlet Piping Surface of the ceiling Vent-Pipe Air Passage Air Strainer (Field Supply) Electrical Box Support Board (Field Supply) Service Access Panel The indoor unit is not designed for the places (B)Install the indoor unit and components that need quiet environment .Install the...
Suspension bolts (1)Select final location and installation direction of the indoor unit paying careful attention to the space for the piping, wiring and maintenance. (2)Using suspendion bolts to install the indootr (unit:mm) unit.Check the celing whether is strong enough to support the indoor unit.Plase reinforce the ceiling Air Inlet before installation if it is not safe.
Page 14
4.3.3 Hanging Indoor Unit Install the indoor unit and the support board using bolts (M12)as shown in Fig 4.4. Adjust the indoor unit installed to the preconcerted height. Hook the suspendion bracket to the nut and washer of rach hanging bolt. Check to ensure the indoor unit is horizontally.
Page 15
Connect the duct as follows. <Air Inlet> Connect the duct with flange inlet together. Seal the pontes between the flange inlet and duct using the aluminous adhesive Tape. <Air Outlet> Connect the duct with flange outlet together. Seal the pontes between the flange outletand duct using the aluminous adhesive tape.
Page 16
(unit:mm) Discharge gas inside And remove the cap Gas Pipe Cool by a wet cloth Liquid Pipe An excess or a shortage of refrigerant is the main cause of trouble to the units. Charge the correct refrigerant quantity.
6.Drain Piping Do not connect the drain pipe with The drain pipe must be installed as the sanitary or sewage piping or any other following figure to avoid bring scales due to drainage piping. the congeal and leakage. When the common drain piping is The positon of the drain piping connection connected with other indoor units, please is shown in Fig 6.1.
Page 18
Do not connect cable of remote control switch and operating wires with power supplyand earth wires together.Keep 50MM All the materials and components should away from each other. comply with local statutes. Use appointed wires,and ensure the terminal Only brass wires are allowed. fixed.