If the unit is supplied with AC the system outputs LT/LQ/HQ are disabled. Switching on the system The LSE-D16 Indicator unit has no master switch. The system is alive as soon as the power supply has been switched on. A switch must be provided in the building installation as a cut-off device. The switch must be labelled appropriately, must be in the vicinity of the equipment and must be easily accessible to the user.
Page 3
Schematics The outputs LT (Lamp test), LQ (Lamp ack.) and HQ (Horn ack.) are only enabled using a DC power supply. The LT, LQ and HQ functions can be customised, see page 9, output functions. The outputs are designed as a current sink and are not potential-free.
Control elements The following buttons are integrated in the front of the unit: Horn acknowl. The output 9, Horn acknowledgement is activated The output 10, Lamp acknowledgement is Lamp acknowl. activated All LEDs, the buzzer as well as the lamp test Lamp acknowl.
Power up the unit and push the HQ and LT keys at the same time within 10 seconds. If no other keys are pressed within 5 seconds, LSE-D16 will switch back to operating mode. If additional keys are pressed, the programming mode remains active for 30 seconds.
Page 6
When the programming mode is activated, LSE-D16 indicator unti starts at the level 1. The levels can be changed in active programming mode using the HQ and LT navigation keys. If for example Level 2 is active on operating input 1, pushing the HQ keys switches the LSE-D16 indicator unit to level 1.
Page 7
LQ and LT output normally open NO LQ and LT output normally closed NC Not used Not used Advanced programming levels 4-6 off Advanced programming levels 4-6 on The functionality of the LSE-D16 indicator unit enhanced continuously. Older units do not cover all described functions.
Page 8
Level 4 Signalisation: Power-LED blinking green LQ-LED blinking magenta In level 4, the LT output (terminal 8) can be switched to common output priority 2. As soon as at least one input of the group 1 is assigned to the common output priority 2, the function is activated.
Functionality Indicator unit The LEDs on the front of the unit are an image of the associated inputs. Output functions Co. Basic function factory setting Alternative function Setting location LT-Output active for 500ms Common Output Prio. 2 Level 3 DIP 16 when LT button is pressed for inputs of group 1 + Level 4 *...
Factory settings The LSE-D16-24-AB is delivered with the following settings: - Level 1: All inputs of group 1 = Closing contact NO - Level 2: All inputs of group 2 = Closing contact NO - Level 3: All virtual DIP-Switches...