Fitting: The BM Basic Module the RM Relay Module and the CIM Connector of the LSC System are fitted on top-hat mounting rails (DIN rails). The PM Panel Module is fitted into a control panel.
System features Modular system: For the processing of new value/first-up value alarms in accordance with DIN 19235: o Building services and building automation o Control systems o Process automation o Power transmission, power distribution o Transport o Communication On-Delay: Individually On-delay setting for all in- and outputs up to 47 minutes Serial interface: For networking (BUS coupling)
(see Technical Data). Voltage which is too high or false polarity of the voltage can lead to damage of the LSC System. After switching on the voltage supply of the LSC System (system voltage) the green LED "POWER ON"...
Warning: If you are using a single Basic Module BM the address has to be set to the stand alone mode (all LED are blinking) which is factory setting. Otherwise, a bus error will occur. Important: If you are in the module ID address setting process and do not press any button for six seconds, the module will switch back to operation mode without saving your changes.
Failure neighbour module: The next module has lost it’s connection or does not work properly . Steady light flashing Important: After having successfully resolved a CAN-bus error, it is recommended to completely restart the LSC system by turning off an on again the supply voltage.
Installation check list Checkpoint Module Connectors Installation Check Supply voltage Power supply Alarm voltage Power supply Supply voltage (connection) First Switch ON 1 Termination resistor Last Switch ON 1 Alarm inputs + 8-15 Alarm inputs - Horn acknowledgement + Horn acknowledgement - Lamp acknowledgement + Lamp acknowledgement - Lamp test +...
Basic Module BM Application & Characteristics The BM Basic Module is the foundation stone of the modularly expandable LSC product family. The BM Basic Module is supplied in the installation housing for top-hat rail mounting. o 8 operation indicator o Integrated buzzer...
Relay Module RM Application & Characteristics The Relay Module RM provides 8 potential free contacts which could be used to build an external signalising or switch other devices. The BM Basic Module is supplied in the installation housing for top-hat rail mounting. o 8-channel relay module o Contact load carrying up to 250 VAC / 3 A per relay output o Normally open or normally closed current principles...
Panel Module PM Application & Characteristics The Panel Module PM acts as an external display in cabinet fronts. It is driven by the BM to which it is connected. The maximum distance between PM and BM is 3 meters. o 8 operation indicator o Integrated buzzer o RS 232 interface o Integrated buttons: Lamp test, Horn acknowledgement and Lamp acknowledgement...
Wiring diagram: Bus connector CIM Application & Characteristics When you are using modules at different venues, the CIM bus connector is the interface between the cabling. The CIM provides a plug for the standard BCC cable on one side and cage clamp connectors on the other side.