Toshiba RAV-HM901FT-E Installation Manual page 21

Hide thumbs Also See for RAV-HM901FT-E:
Table of Contents

Advertisement

 Filter sign setting
According to the installation condition, the filter sign
term (Notification of filter cleaning) can be changed.
Follow to the basic procedure.
1
2
3
4
5
(
).
3
• For the "Code (DN)" in Procedure
, specify
3
• For the "Data" in Procedure
, select the Data of
filter sign term from the following table.
Data
Filter sign term
0000
None
150 H
0001
(Factory default)
0002
2500 H
0003
5000 H
0004
10000 H
 To secure better effect of
heating
When it is difficult to obtain satisfactory heating due to
installation place of the indoor unit or structure of the
room, the detection temperature of heating can be
raised. Also use a circulator or other machinery to
circulate heat air near the ceiling.
Follow to the basic procedure.
1
2
3
4
5
(
).
3
• For the "Code (DN)" in Procedure
, specify
3
• For the "Data" in Procedure
, select the Data of
shift value of detection temperature to be set up from
the following table.
Data
Detection temperature shift value
No shift
0000
(Factory default)
0001
+1°C
0002
+2°C
0003
+3°C
0004
+4°C
0005
+5°C
0006
+6°C
39-EN
 8°C operation
Pre-heating operation can be set for cold regions
where room temperature drops to below zero.
Follow to the basic procedure.
1
2
3
4
5
(
).
[0001]
.
• For the "Code (DN)" in Procedure
[00d1]
.
• For the "Data" in Procedure.
Data
8°C Operation setting
None
0000
(Factory default)
0001
8°C Operation setting
 Communication type
When connecting to an indoor unit or central controller
dedicated to TCC-Link, it is necessary to change to
TCC-Link.
Follow to the basic operation procedure.
1
2
3
4
5
(
).
• For the "Code (DN)" in Procedure
[00FC]
.
3
• For the "Data" in Procedure
, select the Data
[0000]
(TCC-Link).
Data
Communication type
[0006]
.
0000
TCC-Link
TU2C-Link
0004
(Factory default)
 Fan speed setting when
thermostat-OFF in cooling
mode
Set the fan speed when the room temperature
3
reaches the set temperature in the cooling mode.
, specify
Follow to the basic operation procedure.
1
2
3
4
(
• For the "Code (DN)" in Procedure
[009A]
.
• For the "Data" in Procedure
speed when thermostat-OFF in cooling mode from
the following table.
Data
0000
0001
 Installing optional parts
3
, specify
When installing optional parts, data setup may be
required with remote controller.
Be sure to set the data, according to Installation
Manual for optional parts.
 Others
The following functions can be used with this model.
Refer to the Service Manual for more information.
• Rotation / backup operation
• Free cooling
• Secondary heating
• Power shift
– 20 –
5
).
3
, specify
3
, select the Data of fan
Fan speed when thermostat-OFF
in cooling mode
Remote controller setting
Extremely low speed (UL)
(Factory default)
40-EN