Single stage heat/cool real time pricing system

Advertisement

Quick Links

O M N I S T A T
ELECTRONIC COMMUNICATING THERMOSTAT
Installation Manual
RC-81 Single Stage Heat/Cool
Real Time Pricing System
Document Number 13I00-2
January, 1997

Advertisement

Table of Contents
loading

Summary of Contents for HAI Omnistat RC-81

  • Page 1 O M N I S T A T ELECTRONIC COMMUNICATING THERMOSTAT Installation Manual RC-81 Single Stage Heat/Cool Real Time Pricing System Document Number 13I00-2 January, 1997...
  • Page 2 Copyright © 1997 Home Automation, Inc. All Rights Reserved...
  • Page 3: Table Of Contents

    CONTENTS ........DESCRIPTION ........INSTALLATION .
  • Page 4: Description

    DESCRIPTION The RC-81 is a precision digital thermostat with Real Time Pricing, designed for 24 VAC single stage heating and cooling systems. It has the capability of being controlled both locally and by remote control. It offers programmability, stand alone operation, and robust, optically isolated communications with automation systems, utility control systems, and personal computers.
  • Page 5: Location

    LOCATION When replacing an existing thermostat, install the RC-81 in the same location. If the existing location doesn't meet the following criteria, choose a new location to mount the RC-81. When choosing a location for the thermostat: 1. Ensure that the thermostat is mounted about 5 feet above the floor and is at least 2 feet from an outdoor wall.
  • Page 6: Mounting

    MOUNTING When mounting the RC-81, grasp the thermostat by the sides, avoiding the keys, and unsnap the base from the face. Holding the base to the wall so that the word "TOP" is upright and facing you: 1. Mark the two mounting holes on the wall using a pencil. 2.
  • Page 7 Connect each wire to the terminal strip on the thermostat base per the wiring diagram for your system application - See Figures 4 - 8. Form the thermostat wiring so that the cable lies flat between the terminal strip and the center of the thermostat base - See Figure 2. Figure 2 - Forming thermostat wiring If a remote system is being used with the thermostat, connect the...
  • Page 8 Align the tabs of the thermostat face with the slots of the thermostat base. Gently push the thermostat face into the thermostat base locking it into place - See Figure 3. SLOT FACE TEMPERATURE BASE WALL SENSOR Figure 3 - Mounting thermostat face to thermostat base Note: Be sure that the thermostat temperature sensor is standing up, and...
  • Page 9: Typical Wiring Diagrams

    TYPICAL WIRING DIAGRAMS CAUTION 1. Be sure to disconnect the power to the control transformer before removing or installing thermostat. 2. Do not short gas valve, fan, heat relay, or cool relay... even momentarily. This will blow a non-replaceable fuse. 3.
  • Page 10 24VAC CONTROL TRANSFORMER RELAY (IF USED) HEAT RELAY (OR GAS VALVE) COMMON Figure 5 - Single stage heat only thermostat 24VAC CONTROL TRANSFORMER RELAY COOL RELAY COMMON Figure 6 - Single stage cool only thermostat...
  • Page 11 24VAC CONTROL TRANSFORMER RELAY COOL RELAY HEAT RELAY COMMON Common wire is not required in most heat/cool installations. Use only if heat, cool, or fan relay cannot supply 15mA to power thermostat, without activating. Figure 7 - Single stage heat/cool thermostat 24VAC (RC) CONTROL TRANSFORMER...
  • Page 12: Power Up

    POWER UP 1. Double check wiring, be sure that there are no stray wires or wire strands at the connections. 2. It is not necessary to connect the remote system (COMM) cable at this time. 3. Connect power to the control transformer and system. The display will show all segments for about 5 seconds.
  • Page 13: Installer Setup

    INSTALLER SETUP This section describes the items that the installer must setup as part of the thermostat installation. The Installer Setup mode is used to configure the general operating parameters of the thermostat. When in Installer Setup mode: 1. The small digits on the top of the display are the item number. 2.
  • Page 14: Address

    The word "default" indicates the initial setting when the thermostat is delivered from the factory. 00 Address If you are using Communications Mode 0 or 1, and you are installing more than one thermostat, each must be set to a consecutive address, starting at 1.
  • Page 15: Display Options

    03 Display options The thermostat can be configured to display the following attributes: WITH RTP* Celsius am/pm time format programmable Fahrenheit am/pm time format programmable Celsius 24 hour time format programmable Fahrenheit 24 hour time format programmable Celsius am/pm time format non-programmable Fahrenheit am/pm time format...
  • Page 16: Cool Setpoint Limit

    05 Cool setpoint limit This item is used to limit the temperature setting in cool mode. The desired cool setting can never be set below this setting. The default setting is 51. 06 Heat setpoint limit This item is used to limit the temperature setting in heat mode. The desired heat setting can never be set above this setting.
  • Page 17: Cooling Minimum On/Off Time

    A setting of 0 will disable this feature. No anticipation Normal anticipation Maximum anticipation The following settings are recommended: Forced air systems Radiant systems A lower setting will decrease the tendency to turn off the heating system before the desired heat setting is reached. If the heating system response time is slower, as are most radiant heating systems, a higher number will help maintain an even space temperature.
  • Page 18: Heating Minimum On/Off Time

    (1 = - 29 to 59 = + 29 - Seconds per day - 30 = No change) The default setting is 30. Note: If an HAI automation system is being used, the controller system time is sent to the thermostat every minute. This adjustment will have no effect.
  • Page 19: Owner's Manual

    OWNER'S MANUAL Following Installer Setup, check the option boxes ( ) in the Owner's Manual according to the configuration of the thermostat. QUICK-REFERENCE SETUP GUIDE This table displays each Installer Setup item with it's default setting. The column labeled "CURRENT" can be used to write down the current settings if any changes are made to the default settings.
  • Page 20: Remote System Wiring Diagrams

    Run a 3 (or 4) conductor wire from the HAI system to the thermostat location. All thermostats on an Omni, OmniPro, or Aegis controller are connected to Zone 16 and Output 8.
  • Page 21: Troubleshooting Tips

    TROUBLESHOOTING TIPS SYMPTOM ACTION TO TAKE Thermostat Dead 1. Check power to the thermostat 2. Check wiring diagrams 3. Check thermostat temperature sensor Thermostat will not operate with a damaged temperature sensor SYMPTOM ACTION TO TAKE Fan, Heat, Or Cool 1.
  • Page 22 SYMPTOM ACTION TO TAKE Temperature 1. Allow 30 minutes for thermostat to Reading Incorrect adjust to room temperature 2. Adjust calibration offset 3. Change setup option to display F or After installation, allow the thermostat up to 30 minutes for an accurate temperature reading SYMPTOM ACTION TO TAKE...