O M N I S T A T ELECTRONIC COMMUNICATING THERMOSTAT Installation Manual RC-100 Heat Pump 2 Stage Heat / 1 Stage Cool Document Number 13I00-3 January, 1997...
DESCRIPTION The RC-100 is a precision digital thermostat specifically designed for heat pumps. It has the capability of being controlled both locally and by remote control. It offers programmability, stand alone operation, and robust, optically isolated communications with automation systems, utility control systems, and personal computers.
LOCATION When replacing an existing thermostat, install the RC-100 in the same location. If the existing location doesn't meet the following criteria, choose a new location to mount the RC-100. When choosing a location for the thermostat: 1. Ensure that the thermostat is mounted about 5 feet above the floor and is at least 2 feet from an outdoor wall.
MOUNTING When mounting the RC-100, grasp the thermostat by the sides, avoiding the keys, and unsnap the base from the face. Holding the base to the wall so that the word "TOP" is upright and facing you: 1. Mark the two mounting holes on the wall using a pencil.
Page 6
Connect each wire to the terminal strip on the thermostat base per the wiring diagram for your system application - See Figures 4 - 5. Form the thermostat wiring so that the cable lies flat between the terminal strip and the center of the thermostat base - See Figure 2. Figure 2 - Forming thermostat wiring If a remote system is being used with the thermostat, connect the...
Page 7
Align the tabs of the thermostat face with the slots of the thermostat base. Gently push the thermostat face into the thermostat base locking it into place - See Figure 3. SLOT FACE TEMPERATURE BASE WALL SENSOR Figure 3 - Mounting thermostat face to thermostat base Note: Be sure that the thermostat temperature sensor is standing up, and...
WIRING DIAGRAMS CAUTION 1. Be sure to disconnect the power to the control transformer before removing or installing thermostat. 2. Do not short compressor relay, reversing relay, aux heat relay, fan relay or fault relay... even momentarily. This will blow a non-replaceable fuse. 3.
(usually accessories to a heat pump), are not used. The RC-100 automatically controls auxiliary heat efficiently. The RC-100 requires at least 1 stage of auxiliary heat enabled at all times. If the heat pump is equipped with an outdoor...
POWER UP 1. Double check wiring, be sure that there are no stray wires or wire strands at the connections. 2. It is not necessary to connect the remote system (COMM) cable at this time. 3. Connect power to the control transformer and system. The display will show all segments for about 5 seconds.
INSTALLER SETUP This section describes the items that the installer must setup as part of the thermostat installation. The Installer Setup mode is used to configure the general operating parameters of the thermostat. When in Installer Setup mode: 1. The small digits on the top of the display are the item number. 2.
The word "default" indicates the initial setting when the thermostat is delivered from the factory. 00 Address If you are using Communications Mode 0 or 1, and you are installing more than one thermostat, each must be set to a consecutive address, starting at 1.
Page 14
* Energy Efficient Control (EEC) of Auxiliary Heat: Select 0, 1, 4, 5 to enable EEC, or 8, 9, 12, 13 to disable EEC display. See Owner's Manual for description of EEC. The default setting is 1.
In most heat pump installations, the auxiliary heat is electric resistance heat and the Energy Efficient Control (EEC) should be turned on (settings 0, 1, 4, 5). If the heat pump is equipped with a more efficient auxiliary heat, such as hot water supplied by a gas water heater, you may want to turn EEC off (settings 8, 9, 12, 13).
05 Cool setpoint limit This item is used to limit the temperature setting in cool mode. The desired cool setting can never be set below this setting. The default setting is 51. 06 Heat setpoint limit This item is used to limit the temperature setting in heat mode. The desired heat setting can never be set above this setting.
(1 = - 29 to 59 = + 29 - Seconds per day - 30 = No change) The default setting is 30. Note: If an HAI automation system is being used, the controller system time is sent to the thermostat every minute. This adjustment will have no effect.
This item logs the amount of time (hours) that the heating and cooling system was in operation last week. ANTICIPATION RC-100 anticipation is performed electronically and is independent of the type and load of the components in the heating and cooling equipment.
QUICK-REFERENCE SETUP GUIDE This table displays each Installer Setup item with it's default setting. The column labeled "CURRENT" can be used to write down the current settings if any changes are made to the default settings. Item Number Description Default Current Address Communication mode System options...
Run a 3 (or 4) conductor wire from the HAI system to the thermostat location. All thermostats on an Omni, OmniPro, or Aegis controller are connected to Zone 16 and Output 8.
Page 21
Figure 6 - Hookup to an HAI system Additional thermostats are connected in parallel. They may be connected in home-run or daisy chain configuration. REMOTE DAY/NIGHT SETBACK SWITCHES The thermostat can be connected to a remote system or remote switch. A signal can be sent from the remote location to change the thermostat temperature settings from the "DAY"...
TROUBLESHOOTING TIPS SYMPTOM ACTION TO TAKE Thermostat Dead 1. Check power to the thermostat 2. Check wiring diagrams 3. Check thermostat temperature sensor Thermostat will not operate with a damaged temperature sensor SYMPTOM ACTION TO TAKE Fan, Heat, Or Cool 1.
Page 23
Emergency Heat outdoor thermostat. If so, disconnect it. Heat pump may be equipped with an outdoor thermostat which is overriding Aux Heat when outdoor temperature is above certain level - Disconnect the outdoor thermostat, the RC-100 controls the aux heat automatically...
Page 24
24VAC "HOT" (2): (3): REV VALVE (COOLING) (4): REV VALVE (HEATING) (5): 24VAC COMMON (6): COMPRESSOR W2 (7): AUXILIARY HEAT (8): NOT USED FAULT LED Note: X1 is jumped to C terminal in the RC-100, if X2 is in use.
Need help?
Do you have a question about the RC-100 and is the answer not in the manual?
Questions and answers