QAA73: parameters settable by the installer (service)
When the two PROG keys are pressed simultaneously for at least three
seconds, it is possible to enter the list of parameters to display or to
modify by the installer.
Press one of the PROG keys to change the parameter to display or
modify.
Press [+] or [-] to modify the value displayed.
Press one of the PROG keys again to save changes.
Press the information key ( ) to exit programming.
The following section lists only the most commonly used parameters:
Line
Parameter
70
HC1 Heating curve slope
72
HC1 Max. fl ow temperature
74
Type of building construction
75
Room infl uence
77
Adaptation of heating curve
78
Optimum start control maximum
forward shift
79
Optimum stop control maximum
forward shift
90
Reduced set-point of DHW temperature
91
DHW program
93
ECO function
Brief description of the above parameters:
Line
Parameter
70
Selection of heating curve slope
72
Maximum temperature of central heating fl ow
74
Building insulation type settings
75
Activation/deactivation of the room temperature infl uence. If deactivated the
external sensor must be fi tted
77
Automatic adaptation of the heating curve according to the room temperature
78
Max. advance, referred to the hourly program, of the boiler switching on for the
room temperature optimization
79
Max.advance, referred to the hourly program, of the boiler switching off for the
room temperature optimization
90
ECO function – DHW temperature when the boiler is in OFF mode as programmed
in parameter 91.
91
Selection of the type of hourly program for DHW operation. Selection of DHW
PROG involves the setting of parameters 30÷36
93
Activation of ECO function. Set also parameter 90
Range
Factory setting
2,5...40
15
25...85
85
Heavy,
light
light
on HC1
on HC1
on HC2
on HC1+HC2
none
Inactive –active active
0...360 min
0
0...360 min
0
5...60
35
24 h/day
24 h/day
HC-1h PROG
PROG HC
PROG ACS
without ECO
without ECO
with ECO
When the external probe is connected to the appliance, the selectable
curves are illustrated in graph here below.
TM = range of heating fl ow temperature
Te = external temperature
- fault indication
In case of faults, the QAA73 shows the fl ashing symbol
( )
Press information key
fault detected.
Code Display
10
External probe External sensor faulty or parameter 75 deactivated
20
Boiler probe
50
DHW probe
60
Room sensor
110
Boiler STB
133
No fl ame
151
BMU
160
Fan speed
162
Air pressure switch
164
Heating pressure switch
26
to display the code and the description of the
Fault description
Heating fl ow NTC probe faulty
DHW NTC probe faulty
QAA73 faulty
Safety thermostat operation
Gas supply failure
Boiler PCB error.
Switch-off the power supply of the boiler for 10 seconds
Fan speed threshold not reached
Air pressure switch does not commutate
Hydraulic pressure switch does not commutate
.