1.0 Installation and Startup Guide
Install Environment
Where
The MT-600/8000 Series is designed for industrial. The temperature range of operating
Used
is from 32 to 122 °F (0 to 50 °C), as majority of industrial environments. It may not be
suitable for using in certain outdoor applications. Please consult the factory for
advised usage in outdoor applications.
NEMA
The MT-600/8000 Series front bezel is NEMA 4 rated. When installed properly in a
Rating
NEMA 4 panel, the NEMA 4 rating of the panel will not be compromised. This means
that fluids will not enter the panel during wash downs.
Electrical
The MT-600/8000 Series has been tested to conform to European CE requirements.
Environment
This means that the circuitry is designed to resist the effects of electrical noise. This
does not guarantee noise immunity in severe cases. Proper wire routing and
grounding will insure proper operation.
Mechanical
Avoid installing units in environments where severe mechanical vibration or shocks
Environment
are present.
2.0 Installation Instructions
2.1 Mounting Instructions
2.1.1 Location Considerations
Care should be taken when locating equipment behind the unit to ensure that AC power wiring, PLC
output modules, contactors, starters and relays, and any other source of electrical interference are located
away from the back of the unit.
Particular note should be taken to the position of variable speed drives and switching power supplies.
Their input and load cables should be screened to a central star earth point.
2.1.2 Making a NEMA-4 Mounting
Panel
The unit can be mounted into panels with a depth of 4"(105mm). It is recommended that
Details
the unit be mounted on the front panel of a steel enclosure, through an appropriate
opening*. Allow a clearance of 1"(25mm) around the sides of the unit for mounting
MT-8000 series
1
www.ipc2u.ru
MT-8104iH
Installation Instruction

Advertisement

Table of Contents
loading

Summary of Contents for weintek MT-600 Series

  • Page 1 MT-8000 series MT-8104iH Installation Instruction 1.0 Installation and Startup Guide Install Environment Where The MT-600/8000 Series is designed for industrial. The temperature range of operating Used is from 32 to 122 °F (0 to 50 °C), as majority of industrial environments. It may not be suitable for using in certain outdoor applications.
  • Page 2: Environmental Considerations

    hardware. Allow clearance for cable connections to the back of the unit. Unit depth may vary according to cable type used. Typically, plan a depth to accommodate at least 4”(105mm) behind the panel. This device should be mounted in the vertical position and for use on the flat surface enclosure.
  • Page 3: Grounding Requirements

    Equip ungrounded DC supplies with a resistor and capacitor in parallel to earth ground. This provides a path for static and high frequency dissipation. Typical values to use are 1MOhm and 4700pF. To prevent the HMI from becoming damaged or having sound output Caution ! issues, after turning the device off, please wait 10 seconds before turning the device on again.
  • Page 4: Communications Connections

    The ICS 3-304.81 Safety Recommendations are reproduced by permission of the National Electrical Manufacturers Association from NEMA ICS 3-304 2.3 Communications Connections The ports as you look at the back of the case, are the ports for connecting to a PLC or some external device (Controller Connectors).
  • Page 5 1. Using USB cable mini side plug to HMI and another side plug into PC. The PC will display “Found New Hardware Wizard” dialog. Select “Install from a list or specific location (Advanced)”. 2. Check “Include this location in the search”, and assign the path to install Weintek HMI i Series driver from C:\EB8000\usbdriver.
  • Page 6 2.3.6 Dip Switch SW1 SW2 SW3 SW4 Mode OFF OFF ON Touch Screen Calibrate mode OFF ON Hide MT8000 System Setting Bar OFF ON OFF OFF ON ON Boot Loader mode OFF OFF OFF ON Normal OFF OFF OFF OFF Not Supported SW4 is used for adjusting LCD parameters, please keep it in the manufacturer default position, otherwise incorrect screen display may be occurred.
  • Page 7: Specifications

    Weintek products include the isolated power supply are covered by a limited liability warranty from defects in material and workmanship. This warranty does not apply: (a) if, in the judgment of Weintek, the product fails due to damage from shipment, handling, storage, accident (natural and man-mad) ;...
  • Page 8 4.0 Dimensions of MT-8104iH 286.2mm [11.27"] 259mm [10.20"] R2mm [R0.08"] MT8104iH: 259mm [10.20"] W x 201mm [7.91"] H 257mm [10.12"] DIP SW RESET FUSE FUSE5X20 COM1 [RS485 2/4W] COM3 [RS485] COM1 [RS232] COM3 [RS232] COM2 [RS232] DIP SW & Reset button Com1 RS485、Com3 RS485、Com3 RS232 Fuse Com1 RS232、Com2 RS232...