Trane 4TCC4024A1000A Installer's Manual page 13

Single packaged cooling/electric heat 14 seer convertible, 2 - 5 ton

Advertisement

L L i i f f t t i i n n g g a a n n d d R R i i g g g g i i n n g g
I I m m p p o o r r t t a a n n t t : : Do not lift the unit without test lifting for
balance and rigging. Do not lift the unit in
windy conditions or above personnel. Do
not lift the unit by attaching clevis, hooks,
pins, or bolts to the unit casing, casing
hardware, corner lugs, angles, tabs, or
flanges. Failure to observe these warnings
may result in equipment damage.
1. Before preparing the unit for lifting, check the unit
dimension drawings for center of gravity for lifting
safety (Figures 1 to 6). Because of placement of
internal components, the unit's weight may be
unevenly distributed. Approximate unit weights are
also provided in the unit drawings
N N o o t t e e : : Unit rigging and hoisting requires accessory kit
BAYLIFT002A. It includes a kit of four (4) lifting
lugs.
2. Insert the four lifting lugs in the openings provided
in the drip lip on each end of the unit. A tap or jerk
to the lug will overcome the interference that arises
due to the dimple on the lug.
3. When hoisting the unit, be sure that a proper
method of rigging is used. Use slings and spreader
bars for protection during lifting. Always test-lift the
unit to determine the exact unit balance and
stability before hoisting it to the installation
location.
18-EB30D1-1G-EN
Figure 8. Converting Horizontal to Down Airflow
S S t t e e p p 4 4 — — U U n n i i t t I I n n s s t t a a l l l l a a t t i i o o n n
4. When the curb and air ducts have been properly
installed, the unit is ready to be hoisted to the roof
and set in position.
I I m m p p o o r r t t a a n n t t : : To prevent damage to the sides and top of
the unit when hoisting use "spreader
bars".
I I m m p p o o r r t t a a n n t t : : The unit must be lowered into position. The
P.V.C. rubber tape on the curb flange
permits the unit to be repositioned if
required without destroying the P.V.C.
rubber seals affixed to the mounting curb.
P P l l a a c c i i n n g g t t h h e e U U n n i i t t o o n n t t h h e e M M o o u u n n t t i i n n g g C C u u r r b b
1. The unit is designed with a perimeter drip lip that is
lower than the unit base pan.
2. Position the unit drip lip down over and in contact
with the outside corner of the curb.. Continue to
lower the unit on top of the curb, with the unit drip
lip astraddle, and in contact with, both the end and
side rail of the curb. The unit should now rest on
top of the curb. Use the extreme mounting kit,
BAYEXMK001A, to add additional hold down
strength to the mounting.
N N o o t t e e : : The ductwork is installed as part of the curb
installation. Do not attach ductwork to the unit
and lower the unit with ductwork onto the curb.
13