Download Print this page
Trane ComfortLink II Charge Assist 4TTZ0 Series Installer's Manual
Trane ComfortLink II Charge Assist 4TTZ0 Series Installer's Manual

Trane ComfortLink II Charge Assist 4TTZ0 Series Installer's Manual

Air conditioner/heat pump

Advertisement

Quick Links

ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES
IMPORTANT — This Document is customer property and is to remain with this unit. Please return to service information pack upon
completion of work.
These instructions and illustrations do not cover all varia-
tions in systems nor provide for every possible contingency
to be met in connection with installation. All phases of this
installation must comply with NATIONAL, STATE AND
LOCAL CODES. Should further information be desired or should
particular problems arise which are not covered sufficiently for the
purchaser's purposes, the matter should be referred to your install-
ing dealer or local distributor.
a. GeneraL
WarnInG
!
this information is intended for use by individuals pos ses s ing
adequate backgrounds of electrical and mechanical experience. any
attempt to repair a central air condition ing product may result in
personal injury and or property damage. the manufacturer or seller
cannot be respon sible for the interpretation of this information, nor
can it assume any liability in connection with its use.
NOTICE:
Trane has always recommended installing Trane approved
matched indoor and outdoor systems.
The benefits of installing approved matched systems are maxi-
mum efficiency, optimum performance and best overall system
reliability.
WarnInG
!
these units use r-410a refrigerant which operates at 50 to 70%
higher pressures than r-22. Use only r-410a approved service
equipment. refrigerant cylinders are painted a "rose" color to
indicate the type of refrigerant and may contain a "dip" tube to allow
for charging of liquid refrigerant into the system. all r-410a systems
use a Poe/aB oil that readily absorbs moisture from the atmosphere.
to limit this "hygroscopic" action, the system should remain sealed
whenever possible. If a system has been open to the atmosphere for
more than 4 hours, the compressor oil must be replaced. never break
a vacuum with air and always change the driers when opening the
system for component replacement. for specific handling concerns
with r-410a and Poe/aB oil, reference retrofit Bulletin trn-aPG02-
en. check for transportation damage after unit is uncrated. re port
promptly, to the carrier, any damage found to the unit.
caUtIon
!
UnIt contaInS r-410a refrIGerant!
R-410A OPERATING PRESSuRE EXCEEDS THE
LIMIT OF R-22. PROPER SERVICE EQuIPMENT IS
REQuIRED. FAILuRE TO uSE PROPER SERVICE
TOOLS MAY RESuLT IN EQuIPMENT DAMAGE OR
PERSONAL INJuRY.
ServIce
uSE ONLY R-410A REFRIGERANT AND
APPROVED POE/AB COMPRESSOR OIL.
Installer's Guide
air condi
4ttZ0/4tWZ0 with comfortLink
1
Check for transportation damage after unit is uncrated. Report
promptly, to the carrier, any damage found to the unit.
To determine the electrical power requirements of the unit, refer
to the nameplate of the unit. The electrical power available must
agree with that listed on the nameplate.
B. LocatIon and PreParatIon of the UnIt
(INFORMATION APPLICABLE TO HEAT PUMPS ONLY:)
The Heat Pump has been designed and manufactured to withstand
and operate in severe winter conditions. However, there are pre-
cautionary steps which should be taken at the time of installation
which will help assure the efficient operation of the unit. It is rec-
ommended that these precautions be taken for units being
installed in areas where snow accumulation and prolonged
below freezing temperatures occur.
1. Units should be elevated three (3) to twelve (12) inches above
2. If possible, avoid locations that are likely to accumulate snow
3. Avoid locating the unit where condensation and freezing of de-
4. Avoid locating the unit under the eaves or other overhead
tioner/
heat Pump
II and charge assist
Single Unit Installation
1' Behind
the pad or roof top, depending on local weather. This additional
height will allow better drainage of snow and ice (melted dur-
ing defrost cycle) prior to its refreezing. This should prevent a
build-up of ice around the unit which occurs when unit is not
elevated. Insure that drain holes in unit base pan are
not obstructed preventing draining of defrost water.
drifts. If not possible, a snow drift barrier should be installed
around the unit to prevent a build-up of snow on the sides
of the unit and should be of sufficient distance from the unit
to prevent restriction of airflow to and from the unit. Also
allow for proper maintenance space. The barrier should be
constructed of materials which will blend in with the building
design.
frost vapor may annoy the customer. For instance, installing
the unit under a bedroom, kitchen, or picture window may be
annoying to the customer since condensate and fog will occur
during the defrost cycle.
structures as sizeable icicles may form and the unit may be
damaged by these falling icicles.
18-Bc53d2-3
5' Above
Unrestricted
3'

Advertisement

loading
Need help?

Need help?

Do you have a question about the ComfortLink II Charge Assist 4TTZ0 Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Trane ComfortLink II Charge Assist 4TTZ0 Series

  • Page 1 NOTICE: To determine the electrical power requirements of the unit, refer Trane has always recommended installing Trane approved to the nameplate of the unit. The electrical power available must matched indoor and outdoor systems.
  • Page 2 Service Facts. Charge level can always be verified with the Refrigerant Charging Chart found in the Service Facts. 1. Determine the most practical way to run the lines. 2. Consider types of bends to be made and space limitations. 18-BC53D2-3 © 2009 Trane...
  • Page 3 Installer’s Guide NOTE: GaS LIne BaLL ServIce vaLve DO NOT VENT REFRIGERANT INTO THE ATMOSPHERE. 1/4 tUrn onLy NOTE: coUntercLockWISe for fULL oPen A 3/16" Allen wrench is required to open liquid line service valve. PoSItIon A 1/4" Open End or Adjustable wrench is required to open gas line valve.
  • Page 4 Installer’s Guide f. defroSt controL (HEAT PUMPS ONLY) G. coMPreSSor Start UP After all electrical wiring is complete, SET THE COM- The demand defrost control measures heat pump outdoor ambi- FORTLINK™ II CONTROL SWITCH IN THE OFF POSITION SO ent temperature with a sensor located outside the outdoor coil. A COMPRESSOR WILL NOT RUN, and apply power by closing the second sensor located on the outdoor coil is used to measure the system main disconnect switch.
  • Page 5 Installer’s Guide fIeLd WIrInG dIaGraM coMMUnIcatInG Indoor UnIt – coMMUnIcatInG oUtdoor UnIt note: For non- communicating systems use 24-volt harness accessory BAYACHP024A. 18-BC53D2-3...
  • Page 6 Installer’s Guide coMMUnIcatInG Indoor UnIt WIth 24v coMfort controL, 24v 2-StaGe or 2-SteP cooLInG 18-BC53D2-3...
  • Page 7 Installer’s Guide coMMUnIcatInG Indoor UnIt WIth 24v coMfort controL, 24v 2-StaGe or 2-SteP heat PUMP 18-BC53D2-3...
  • Page 8 Installer’s Guide oUtdoor controL Board – charGe aSSISt™ Port charGe aSSISt™ note: Charge Assist ™ port is designed for liquid refrigerant charging. dIrectIon for charGe aSSISt™ NOTE: Outdoor Temperature (ODT) must be between 55°F If the system charge is low, the “ADD” LED will turn on and stay and 120°F.
  • Page 9 Installer’s Guide SUBcooL charGInG taBLe correctIonS SuBCOOL CHARGING TABLE CORRECTIONS FOR LINE LENGTH AND RISE TABLE A TABLE B 4TEE3_03 Air Handler Downflow & Horizontal Left Only These matches 4TXCB003 Coil Downflow & Horizontal Right Only All other approved, matched systems. ONLY 4TXCC006 Coil Downflow &...
  • Page 10: Troubleshooting Chart - What To Check

    Please refer to Application Guide SS-APB006-EN: shifted during shipment. Adjust tubing if necessary so tubes do not rub Trane - Sea Coast Applications. against each other when the unit runs. Also be sure that wiring con- nections are tight and wire routing is secure.
  • Page 11 Installer’s Guide 4ttZ0/4tWZ0 oUtLIne draWInG note: aLL dIMenSIonS are In MM (IncheS). ModeLS BaSe 4TTZ0024A 1369 (53 7/8) 946 (37-1/4) 870 (34-1/4) 152 (6) 98 (3-7/8) 219 (8-5/8) 86 (3-3/8) 1035 (40 3/4) 4TWZ0024A 4TTZ0036A 4TWZ0036A 4TTZ0048A 1369 (53 7/8) 946 (37-1/4) 870 (34-1/4) 152 (6)
  • Page 12: Installer's Guide

    7. Indoor coil drain line drains freely. Pour water into drain pan ................. [ ] 02/09 Trane Trane has a policy of continuous product and product data improvement and it reserves the right to change www.trane.com design and specifications without notice.