15.3.

Adjusting Maximum Capacity

Via Adjusting of room Comfort setpoint button set boiler capacity to 100%. Later when you
1.
press OK button, boiler will start working at medium capacity
2.
According to flue gas measurement values at maximum capacity, use A and C points for gas
flow rate. Use A point for coarse setting for gas flow rate and C point for precise gas flow rate.
For both points, turning clockwise increases flow rate and turning counter clockwise
decreases flow rate.
Check the emission values at minimum and maximum capacities again and adjust combustion parameters
precisely by following above steps.
After adjustment of parameters are finished, close all measurement points as they will be leak proof.
Flue gas emission values and flue gas temperature limit values are given at below table:
15.4.

Adjsuting Time Schedule

1. Press ESC button several times in order to get main screen.
2. Press "OK" button when you are at main screen. "Time and day adjusment" line will be seen on the screen.
Press "OK" again and select related line.
3. In order of clock, year and month informations will blink.
4. Set the blinking value and press "OK" after each setting.
14.12.2021 Rev. 03
O2
<5,5
CO
<50
CO2
8,4-9
Flue Gas
<80
Temperature
.
%
ppm
%
°C