13.2.

Checks During Commissioning

Ø Switch on the device.
Ø Ensure the soundness of oil circuit and water system.
Ø When the boiler is in operation, check sufficiency of flue and water pipes.
Ø Check the soundness of condensation system and ensure its correct operation.
Ø Make sure that water circulation takes place properly.
Ø Make sure that gas valve is operating correctly.
Ø Check the eligibility of values at minimum and maximum capacities by using a flue gas analyz
Ø Check the compatibility of gas consumption with the values on the technical data table.
Ø Make sure that parameters are programmed correctly.

14. ADJUSTING COMBUSTIN PARAMATERS

Instructions below are specially prepared for ECODENSE service technicians. Before shipment
parameters of all the boilers are adjusted at suitable capacity and pressure at factory's test stand. Settings
mentioned below are for combustion optimization at field conditions. Appropriate allen keys and wrenchs
must be used for screws and caps. Gas and air values must be adjusted by using a flue gas analyser.
14.1.

Adjustment and Measurement Points

A: Throttle Adjustment Point
B: Gas Feed Pressure Measurement Point
C: Offset Adjustment Point
D: Burner Gas Pressure Managament Point
During adjusting parameters follow below step;
1. Minimum capacity activation and combustion adjustment
2. Medium capacity emission control
3. Maximum capacity combustion adjustment and control
4. Minimum-maximum capacity combustion adjustment control
14.12.2021 Rev. 03