Portable flexible version rectifier monitoring system (78 pages)
Summary of Contents for DynAmp LKP-180
Page 1
MODEL LKP-180, LKP-300, & LKP-400 DIRECT CURRENT METERING SYSTEMS Installation, Operation and Service Instructions Manual Item No. 041749 Rev. K DynAmp, LLC 3735 Gantz Road Phone +1 614.871.6900 www.dynamp.com Grove City, Ohio 43123 USA Fax +1 614.871.6910 help@dynamp.com...
Page 5
Use of the equipment in a manner not specified by the manufacturer can impair GENERAL the protection provided within. DynAmp does not assume liability for the customer’s failure to comply with the rules and requirements provided in this manual. This equipment is designed to be connected to hazardous electric voltages.
Page 7
Installation, Operation and Service Manual LKP Series DynAmp, LLC Customer Support For further assistance, contact DynAmp Customer Support at: Americas: Telephone: +1 614.871.6900 Fax: +1 614.871.6910 8:00 AM to 5:00 PM USA Eastern Time From first Sunday in November to second Sunday in March – 13:00 GMT to 22:00 GMT From second Sunday in March to first Sunday in November –...
Page 9
LKP Series REVISION PAGE Page Change Reason For Revision Date Rev NEW 9/97 Rev A Added LKP-400 information, updated LKP-180 & 300 7/98 Drawings Rev B Updated mounting instructions, accuracy diagnostics 8/99 information, and wiring diagrams. Rev C Warranty, Installation Considerations...
The DynAmp, LLC LKP Series 16 Channel are systems for accurately measuring direct current in a bus. The Models in this series are: LKP-180, LKP-300 and LKP-400. Each model consists of a Measuring Head, a Metering Unit, and multi-conductor cables.
Installation Category Pollution Degree Contingent upon DynAmp, LLC computer analysis of bus system. The LKP systems are factory-set for the correct voltage and frequency (50 or 60 Hz) per customer order. To operate an LKP system at a different line frequency than was ordered, move jumper JP1 (located on the control board inside each module) to the desired frequency.
Page 20
Overall Dimensions, in. (mm): LKP Metering Unit (all) 66 (1676)H x 48 (1220)W x 16 (406)D LKP-180 Measuring Head (Version 1) 78.3 (1989)H x 111.1 (2823)W x 25.2 (640)D LKP-180 Measuring Head (Version 2) 102.2 (2597)H x 101.3 (2572)W x 25.2 (640)D LKP-300 Measuring Head (Version 1) 97.4 (2473)H x 142.8 (3627)W x 25.2 (640)D...
Visible damage must be reported to the carrier immediately. Concealed damage (not evident until the system is operated) must be reported to DynAmp, LLC immediately. For all handling of the Measuring Head, use lifting straps capable of carrying a 4400lbs (2000kg) load.
Warning : Keep all exposed head cable leads from touching the bus, ground, or any support structures. Consult with DynAmp about using a shorting plug at each connector. INSTALLATION PRECAUTIONS (LIVE BUS) If the unit is to be installed on a live bus, the following precautionary measures must be taken before installing the Measuring Head: Make sure that the cables are disconnected from the head during installation.
The general guidelines below should be applied only when a detailed analysis of your bus system is not available. DynAmp, LLC will perform one detailed computer analysis of the proposed location of the Measuring Heads within your bus system at no charge.
As is true with any electronic circuitry, proper maintenance will prolong the service life. DynAmp, LLC recommends the following program be performed at the recommended interval to prevent or detect damage to the LKP system and to ensure continuing high- accuracy performance.
Disconnect power to the system before servicing or replacing fuses. CALIBRATION INTERVALS DynAmp does not specify required intervals of calibration for its products. The end user of the product is responsible for identifying the appropriate interval between calibrations. The intervals should be determined based on the following factors: •...
SPARE PARTS ORDERS - ROUTINE OR EMERGENCY Requests for spare parts should be directed to "Inside Sales" at DynAmp, LLC during normal hours, if possible, or via any method shown above for off-hours. When contacting us, please present as much information as possible, such as the related equipment Model and Serial Numbers, the required part name, DynAmp, LLC item numbers and other identifying or vendor number(s), and your time needs.
Page 47
Installation, Operation and Service Manual LKP Series SERVICE ASSISTANCE For further assistance, contact DynAmp Customer Support at: Americas: Telephone: +1 614.871.6900 Fax: +1 614.871.6910 8:00 AM to 5:00 PM USA Eastern Time From first Sunday in November to second Sunday in March – 13:00 GMT to 22:00 GMT From second Sunday in March to first Sunday in November –...
Page 49
The following is a list of available technical bulletins that contain relevant information in regards to high current measurements and the use of LKP systems. The technical bulletins are available upon request from DynAmp, LLC. Always consult the factory for a list of the latest technical bulletins.
Page 51
Assembly: Supply & SCR Drive PC Board 75B108106 Outline and Mounting: LKP Series 16 Channel Metering Unit 02D107892 Outline and Mounting: LKP-180 Measuring Head (version 1) 02D108148 Outline and Mounting: LKP-180 Measuring Head (version 2) 02D108149 Outline and Mounting: LKP-300 Measuring Head (version 1)
Need help?
Do you have a question about the LKP-180 and is the answer not in the manual?
Questions and answers