Portable flexible version rectifier monitoring system (78 pages)
Summary of Contents for DynAmp LKP-8024
Page 1
Model LKP-8024 DIRECT CURRENT METERING SYSTEMS Installation, Operation and Service Instructions Manual Item No. 041837 Rev. H DynAmp, LLC 3735 Gantz Road Phone +1 614.871.6900 www.dynamp.com Grove City, Ohio 43123 USA Fax +1 614.871.6910 help@dynamp.com...
Page 3
Items and components not manufactured and resold by Seller are warranted by their manufacturer. Warranty repair shall be, at DynAmp’s option, in the form of repair or replacement of the defective items or components. Concerning warranty repairs, DynAmp will be responsible for DynAmp provided time, material and transportation costs (shipping or travel).
Page 5
Use of the equipment in a manner not specified by the manufacturer can impair the protection provided within. DynAmp does not assume liability for the customer’s failure to comply with the rules and requirements provided in this manual. This equipment is designed to be connected to hazardous electric voltages.
Page 7
Installation, Operation and Service Manual LKP Series DynAmp, LLC Customer Support For further assistance, contact DynAmp Customer Support at: Americas: Telephone: +1 614.871.6900 Fax: +1 614.871.6910 8:00 AM to 5:00 PM USA Eastern Time From first Sunday in November to second Sunday in March – 13:00 GMT to 22:00 GMT From second Sunday in March to first Sunday in November –...
Page 9
Deleted text regarding Hall Sensor power supply. 3/01 18, 24 Updated Accuracy Diagnostics & Spare Parts section 04/02 Rev D Update to DynAmp, LLC 12/04 Rev E Update per ECR-1245 – Remove 6-3. “Five Year Service” 11/05 and revised 6.2 (F.)
These instructions apply only to retrofit kits installed on standard systems as originally • supplied by Halmar Electronics or DynAmp. Customer is responsible to verify that the units are standard and do not have non-standard, customer modifications installed. Before installing the upgrade kit, document any modifications and contact DynAmp, LLC Service Department for further written instructions to deal with the non-standard circumstances.
The LKP-8000 Series Replacement Signal Converter Kits permits an economical field conversion and upgrade of an existing FM system. This conversion makes it possible to get many of the benefits of the new DynAmp LKP design, while keeping the existing enclosure, cables, and measuring head.
(located on the control board inside each module) to the desired frequency. Refer to the wiring diagrams for changing the input voltage. When calibrated with at DynAmp, LLC factory after retrofit kit installation. May be 0.5% if not recalibrated. May be 0.2% if calibrated on site with a DynAmp portable measurement system.
24FM Metering Unit conversion. PRELIMINARY PRECAUTIONS DynAmp, LLC recommends that all work be done on a de-energized bus. If this is not possible at your location, shut down the mains power to the 24FM, and observe the WARNINGS and NOTES that follows.
EXPRESSED OR IMPLIED MAY BE AFFECTED. CHECK WITH DynAmp, LLC FOR SPECIFIC DETAILS. CONVERSION PROCEDURE Conversion from the old 24FM Metering System to the new LKP-8024 is described in the following steps. Prior to shutting down the old system, record the “As Found” channel voltages for comparison later to the “After Conversion”...
(to verify no condition exists that may cause damage to the LKP-8024), and the second set after a 24- hour period of time (to thermally stabilize the head). Proceed as follows: a.
Page 25
Installation, Operation and Service Manual LKP Series TABLE 5.1 MEASURING HEAD RESISTANCE CHART -LKP-8024 Measure Between Leads: Desired Value Circuit (Ohms) CABLE TO “1” HALF OF HEAD 25 & 26 25-30 Hall Current - Channels 1, 2. 3 1 & 4 Hall Signal - Channel #1 5 &...
As is true with any electronic circuitry, proper maintenance will prolong the service life. DynAmp, LLC recommends the following program be performed at the recommended interval to prevent or detect damage to the LKP system and to ensure continuing high- accuracy performance.
Installation, Operation and Service Manual LKP Series name; its DynAmp, LLC item number (and other identifying or vendor number(s); and your time needs. An approved Purchase Order Number should be given with your order. RECOMMENDED SPARE PARTS The following table lists the minimum recommended quantities* for spare parts for the LKP meter unit.
Installation, Operation and Service Manual LKP Series SERVICE ASSISTANCE For further assistance, contact DynAmp Customer Support at: Americas: Telephone: +1 614.871.6900 Fax: +1 614.871.6910 8:00 AM to 5:00 PM USA Eastern Time From first Sunday in November to second Sunday in March – 13:00 GMT to 22:00 GMT From second Sunday in March to first Sunday in November –...
The following is a list of available technical bulletins that contain relevant information in regards to high current measurements and the use of LKP systems. The technical bulletins are available upon request from DynAmp, LLC. Always consult the factory for a list of the latest technical bulletins.
Installation, Operation and Service Manual LKP Series 9. DRAWINGS TABLE 9.1 DRAWING LIST DRAWING TITLE NUMBER Schematic: LKP-8024 Power Input 05B108413 Schematic: LKP High Range Module 05B108074 Schematic: CM 4CH Alarm PC Board 05A107144 Schematic: CM 2CH Alarm PC Board...